![Neptune 13458-000 Скачать руководство пользователя страница 112](http://html1.mh-extra.com/html/neptune/13458-000/13458-000_installation-and-maintenance-manual_1668232112.webp)
l
If an individual battery does not hold a voltage of a least
12.6 VDC open circuit after a full charge and a three-hour wait
period under no load, you could have a damaged cell and
require a battery replacement.
l
If battery voltage climbs very rapidly under charge, then falls
rapidly after removing the charge, you could have a damaged
cell and require a battery replacement.
The same battery, Sun Xtender Part No. PVX-1040T, is used
in the 150 W and 220 W solar power options.
Table 26 provides the 120-hour load voltages during the
discharge cycle from full charge to 100% discharge to 10.5V at
25°C (77°F).
DOD (%)
Battery Voltage (volts)
10
12.69
20
12.58
30
12.45
40
12.32
50
12.18
60
12.05
70
11.88
80
11.65
90
11.40
100
10.50
Table 26 – Battery Load Voltage by DOD
These voltages are averages. They vary slightly from battery
to battery even if they are of the same rating. However, they
are a good indicator of state of charge for AGM batteries. This
data is for newer batteries with relatively few cycles. An older
battery measures a lower voltage for a given DOD.
94
R900 Gateway Installation and Maintenance Guide
Appendix A Solar Power Information
Содержание 13458-000
Страница 2: ......
Страница 3: ...R900 Gateway v4 Installation and Maintenance Guide...
Страница 6: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank Chapter 1 Overview 8 R900 Gateway Installation and Maintenance Guide...
Страница 116: ...This page intentionally left blank Appendix A Solar Power Information 98 R900 Gateway Installation and Maintenance Guide...
Страница 149: ......