Neptronic TRT2422 Скачать руководство пользователя страница 8

Rooftop Thermostat Controller

Specification and Installation Instructions

 

www.neptronic.com

 

 

Page | 8

 

30.

 

“Display Temp Sensor” 

   

 

Default: 
Range:  

OFF 
OFF, t10.0 (external temperature sensor 10.0

 

K

 at input #16

)  

In operation mode (page 15), the thermostat can display the temperature from another sensor connected to input #16. This sensor 
is for display purposes only and performs no control functions..  

 

If you select OFF, input #16 is ignored.  

 

If you select t10.0, the thermostat can display temperature sensor connected to input #16. Use a Type III 10k

 

temperature sensor. 

31.

 

“Display Temp Mode” 

   

 

Default: 
Range: 

No  
Yes / No 

If set to “No”, in operation mode (page 15) the thermost displays the time on the first line. If set to “Yes”, in operation mode (page 
15) the thermostat displays the temperature from input #16 on the first line. Also refer to step 30 above. 

32.

 

 “Select DI Contact” 

 

 

Default: 
Range:  

OFF  
OFF, FILt, SEr, Airf 

Select the input signal type for AI1 (analog input 1). 

 

OFF: no signal 

 

FILt: The input is used for a dirty filter contact. When activated, “Filter” and the 

 symbol are displayed. All control modes 

continue to function.  

 

SEr: The input is used to notify that service is required. When activated, “Service” and the 

 symbol are displayed. All 

control modes continue to function. 

 

Airf: The input is used to connect an air flow sensor. When activated, “Airflow” and the 

 symbol are displayed. All 

outputs will be turned off until the issue is corrected. 

33.

 

“Set DI Normal state” 

   

 

Default: 
Range: 

NO (Normally Open) 
NO (Normally Open), NC (Normally Close) 

Seelct the desired normal state of input DI (input #13).  

34.

 

“Enable Anti freeze Protect” 

 

 

Default: 
Range:  

No (disabled) 
No, Yes 

If this option is enabled, heating starts automatically when the temperature drops to 4ºC [39ºF], even if the thermostat is in OFF 
mode. Once the temperature reaches 5ºC [41ºF], the heating stops. 

 

Schedule Mode 

This menu is accessible through normal operation mode.  
1.  The Thermostat Mode selector jumper (JP2) must be set to "RUN" position (Operation Mode). Refer to PCB on page 2. 
2.  Press and hold the 

 button for 5 seconds, the

 symbol appears to indicate that you’re in Scheduling Mode.  

3.  Use the 

 and

 arrow keys to increase or decrease the values. 

4.  Press the 

 and 

 buttons to navigate through the program functions.  

 
The thermostat will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press 
any key for 5 minutes. The changed values will be saved automatically.  

Содержание TRT2422

Страница 1: ...ion Backlit LCD with simple icon and text driven menus Multi level lockable access menu and setpoint Selectable Fahrenheit or Celsius scale Removable connectors TRT2422 Applications 2 Heat 2 Cool Supp...

Страница 2: ...ongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products This precaution will prevent interference with and or...

Страница 3: ...sed in this Manual Temperature Heating Cooling Fan Schedule Mode Timer clock W1 Heating Stage 1 W2 Heating Stage 2 Y1 Cooling Stage 1 Y2 Cooling Stage 2 User Control 1 Inside Temp Sensor Offset Range...

Страница 4: ...Default Range Increment 0 3 C 0 6 F 0 to 5 0 C 0 to 10 F 0 1 C 0 2 F Select the desired dead band value of the heating ramp The heating symbol is also displayed 6 Control Dead Band Cooling Default Ra...

Страница 5: ...p 10 Contact automatically opens at 0 of the demand 13 Select W1 Direct Reverse W1 Default Range dir Direct dir Direct or rEV Reverse Select the direction for the W1 output signal Set dir Direct for n...

Страница 6: ...the demand 20 Select Y1 open Percent Y1 Default Range Increment 20 of demand 0 to 80 range is limited by the close value of step 19 minus 10 5 Select the percentage at which you want Y1 to open at of...

Страница 7: ...symbol is also displayed Temperature Sensor Settings 28 Extern Sensor Temp Default Range OFF OFF t10 0 external temperature sensor 10 0 K at input 14 Select the temperature sensor that will be used b...

Страница 8: ...used to notify that service is required When activated Service and the symbol are displayed All control modes continue to function Airf The input is used to connect an air flow sensor When activated...

Страница 9: ...es 4 enter year Default Range Increment Selection 2010 2010 to 2099 1 Year Select the year 5 enter month Range Increment Selection 01 to 12 January to December 1 month Month Select the month 6 enter d...

Страница 10: ...event 1 cooling setpnt Default Range Increment Display 22 C 72 F 10 to 40 C 50 to 104 F Off 0 5 C 1 F MO Select the desired cooling temperature setpoint for the duration of Event 1 The minimum value i...

Страница 11: ...ontinue Event 1 4 Events Day If the 4 events per day option was selected at step 9 16 e1 Default Range Increment Display 06 00 00 00 to Monday Event 2 start time 15 minutes 15 minutes MO E1 Set the st...

Страница 12: ...t the desired heating temperature setpoint for the duration of Event 2 The maximum value is restricted by the cooling setpoint of Event 2 at step 20 Event 3 4 Events Day If the 4 events per day option...

Страница 13: ...copy Monday s schedule to Tuesday Wednesday Thursday and Friday 28 copy schedul Default Range No No Yes selected day If you do not want to copy a schedule select NO The currently configured days appea...

Страница 14: ...ked Yes No Select No to allow the user to change control modes Select Yes to lock the control mode to the user A lock symbol appears to indicate that the control mode is locked 32 quit Default Range Y...

Страница 15: ...the arrow keys while the temperature is displayed If the setpoint adjustment has been locked Step 29 on page 13 the lock symbol appears Room temperature Appears if setpoint adjustment is locked Change...

Страница 16: ...y on OFF Override Setpoint This function is only available if you have set the used time schedule option to Yes at Step 7 on page 9 When the schedule is triggered the thermostat uses the setpoints def...