9.
“select 2 or 4 events per day”
Default:
Range:
2 Events
2 Events, 4 Events
Select the desired number of events per day. You can choose between 2 events or 4 events per day. This selection will be applied
for each day of the week.
If you selected 2, go to Step 10.
If you selected 4, go to Step 16.
Event 1 (2 Events/Day)
If the “2 events per day” option was selected at step 9.
10.
“e1”
Default:
Range:
Increment:
Display:
6:00
From 00:00 to Monday Event 2 start time minus 15 minutes
15 minutes
MO, E1,
Set the start time for Event 1 on Monday. The Monday Event 1 temperature setting will be effective from the time that is set here
until the time set for the Event 2 on Monday.
11.
“adjust event 1 cooling setpnt”
Default:
Range:
Increment:
Display:
22ºC
[72ºF]
10 to 40ºC
[50 to 104ºF], Off
0.5ºC
[1ºF]
MO, ,
Select the desired cooling temperature setpoint for the duration of Event 1. The minimum value is restricted by the Event 1 heating
setpoint at step 12.
If you select the
Off
option, the thermostat will be off for Event 1
(go to Step 13)
.
12.
“adjust event 1 heating setpnt”
Default:
Range:
Increment:
Display:
20ºC
[68ºF]
10 to 40ºC
[50 to 104ºF]
0.5ºC
[1ºF]
MO, ,
Select the desired heating temperature setpoint for the duration of Event 1. The maximum value is restricted by the cooling setpoint
of Event 1 at step 11.
Event 2 (2 Events/Day)
If the “2 events per day” option was selected at step 9.
13.
“e2”
Default:
Range:
Increment:
Display:
20:00
From Monday Event 1 start time +15 minutes to 23:45
15 minutes
MO, E2,
Set the start time for Event 2 on Monday. The Monday Event 2 temperature setting will be effective from the time that is set here
until the time set for the Event 1 on Tuesday.