![Neptronic TRT2422 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/neptronic/trt2422/trt2422_specification-and-installation-instructions_1668162012.webp)
Rooftop Thermostat Controller
Specification and Installation Instructions
www.neptronic.com
Page | 12
Event 2 (4 Events/Day)
If the “4 events per day” option was selected at step 9.
19.
"E2”
Default:
Range:
Increment:
Display:
20:00
From Monday Event 1 start time +15 minutes to Event 3 start time minus 15 minutes
15 minutes
MO, E2,
Set the start time for Event 2 on Monday. The Monday Event 2 temperature setting will be effective from the time that is set here
until the time set for the Event 3 on Monday.
20.
"adjust event 2 cooling setpnt”
Default:
Range:
Increment:
Display:
28ºC
[82ºF]
10 to 40ºC
[50 to 104ºF], Off
0.5ºC
[1ºF]
MO, ,
Select the desired cooling temperature setpoint for the duration of Event 2. The minimum value is restricted by the Event 2 heating
setpoint at step 21.
If you select the Off option, the thermostat will be off for Event 2 (go to Step 21).
21.
"adjust event 2 heating setpnt”
Default:
Range:
Increment:
Display:
16ºC
[68ºF]
10 to 40ºC
[50 to 104ºF]
0.5ºC
[1ºF]
MO, E2,
,
Select the desired heating temperature setpoint for the duration of Event 2. The maximum value is restricted by the cooling setpoint
of Event 2 at step 20.
Event 3 (4 Events/Day)
If the “4 events per day” option was selected at step 9.
22.
"e3”
Default:
Range:
Increment:
Display:
22:00
From Monday Event 2 start time +15 minutes to Event 4 start time minus 15 minutes
15 minutes
MO, E3,
Set the start time for Event 3 on Monday. The Monday Event 3 temperature setting will be effective from the time that is set here
until the time set for the Event 4 on Monday.
23.
"adjust event 3 cooling setpnt”
Default:
Range:
Increment:
Display:
22ºC
[72ºF]
10 to 40ºC
[50 to 104ºF], Off
0.5ºC
[1ºF]
MO, E3,
,
Select the desired cooling temperature setpoint for the duration of Event 3. The minimum value is restricted by the Event 3 heating
setpoint at step 24.
If you select the Off option, the thermostat will be off for Event 3 (go to Step 25).
24.
"adjust event 3 heating setpnt”
Default:
Range:
Increment:
Display:
20ºC
[68ºF]
10 to 40ºC
[50 to 104ºF]
0.5ºC
[1ºF]
MO, E3,
,
Select the desired heating temperature setpoint for the duration of Event 3. The maximum value is restricted by the cooling setpoint
of Event 3 at step 23.