![Neptronic TRT2422 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/neptronic/trt2422/trt2422_specification-and-installation-instructions_1668162004.webp)
Rooftop Thermostat Controller
Specification and Installation Instructions
www.neptronic.com
Page | 4
2.
“Enable On Off Control Mode”
Default:
Range:
Yes (Enable)
Yes / No
If you select Yes, the user can set the unit to “Off” via the Control Mode (see page 16). If you select No, the “Off” selection does not
appear in the Control Mode.
Control Ramps and Timers
3.
“Control Ramp Heating”
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the heating ramp. The heating symbol is also displayed.
4.
“Control Ramp Cooling”
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the cooling ramp. The cooling symbol is also displayed.
5.
“Control Dead Band Heating”
Default:
Range:
Increment:
0.3ºC
[0.6ºF]
0 to 5.0ºC
[0 to 10ºF]
0.1ºC
[0.2ºF]
Select the desired dead band value of the heating ramp. The heating symbol is also displayed.
6.
“Control Dead Band Cooling”
Default:
Range:
Increment:
0.3ºC
[0.6ºF]
0 to 5.0ºC [0 to 10ºF]
0.1ºC
[0.2ºF]
Select the desired dead band value of the cooling ramp. The cooling symbol is also displayed.
7.
“Anti Cycle Time in Minutes”
Default:
Range:
Increment:
2 minutes
0 to 15 minutes
1 minute
To protect the compressor, set the delay in minutes before activating or reactivating the cooling contact.
8.
“Heating Intgral Time in Seconds”
Default:
Range:
Increment:
0 seconds
0 to 250 seconds
5 seconds
Set the desired value for the heating integration factor compensation. The heating symbol is also displayed.
9.
“Cooling Intgral Time in Seconds”
Default:
Range:
Increment:
0 seconds
0 to 250 seconds
5 seconds
Set the desired value for the cooling integration factor compensation. The cooling symbol is also displayed.