Rooftop Thermostat Controller

Specification and Installation Instructions

 

TRT2422-141202 

 

Page | 1

 

Model 

TRT2422 

Description 

The TRT2422 is a combination controller and thermostat with a 
built-in scheduler, which is designed for simple and accurate 
control of single or dual stage heating/cooling equipment, such as 
rooftop and self-contained units. Its field configurable algorithms 
enable versatile implementation of required control sequences.   

Features 

  Precise temperature control with programmable PI (time 

proportional control algorithm) 

  Configurable scheduler (7 days, 2/4 events) 

  24-hour backup battery for RTC (real-time clock) 

  2 external temperature sensor inputs 

  1 digital input 

  2 heat, 2 cool and 1 fan output 

  Automatic freeze protection 

 Anti-cycling 

protection 

 24Vac 

operation 

  Backlit LCD with simple icon and text driven menus  

  Multi level lockable access menu and setpoint 

  Selectable Fahrenheit or Celsius scale 

 Removable 

connectors 

 

TRT2422 

Applications 

  2 Heat / 2 Cool 

  Support single and two stage equipment 

Technical Specifications 

Power supply 

22 to 26Vac 50/60Hz 

Power consumption 

1VA (excluding output loads) 

Setpoint range 

10ºC to 40ºC [50ºF to 104ºF]  

Inputs 

- Two 10K

 Type III inputs 

- One digital contact (dry contact) 

Outputs 

5 dry contacts, 24Vac, 1A max, 3A in-rush 

External sensor range  

-40ºC to 100ºC [-40ºF to 212ºF] 

Control accuracy 

Temperature: ±0.4ºC [0.8ºF] 

Proportional band 

0.5ºC to 5ºC [1ºF to 10ºF] adjustable 

Electrical connection 

0.8 mm

[18 AWG] minimum 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95% non condensing 

Degree of protection of housing 

IP 30 (EN 60529) 

Weight 

160 g. [0.36 lb] 

Dimensions 
A = 2.85” | 73mm 
B = 4.85” | 123mm 
C = 1.00” | 24mm 
D = 2.36” | 60mm 
E = 3.27” | 83mm

 

A

B

C

D

E

ºF / º C

 

 

 

Содержание TRT2422

Страница 1: ...ion Backlit LCD with simple icon and text driven menus Multi level lockable access menu and setpoint Selectable Fahrenheit or Celsius scale Removable connectors TRT2422 Applications 2 Heat 2 Cool Supp...

Страница 2: ...ongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products This precaution will prevent interference with and or...

Страница 3: ...sed in this Manual Temperature Heating Cooling Fan Schedule Mode Timer clock W1 Heating Stage 1 W2 Heating Stage 2 Y1 Cooling Stage 1 Y2 Cooling Stage 2 User Control 1 Inside Temp Sensor Offset Range...

Страница 4: ...Default Range Increment 0 3 C 0 6 F 0 to 5 0 C 0 to 10 F 0 1 C 0 2 F Select the desired dead band value of the heating ramp The heating symbol is also displayed 6 Control Dead Band Cooling Default Ra...

Страница 5: ...p 10 Contact automatically opens at 0 of the demand 13 Select W1 Direct Reverse W1 Default Range dir Direct dir Direct or rEV Reverse Select the direction for the W1 output signal Set dir Direct for n...

Страница 6: ...the demand 20 Select Y1 open Percent Y1 Default Range Increment 20 of demand 0 to 80 range is limited by the close value of step 19 minus 10 5 Select the percentage at which you want Y1 to open at of...

Страница 7: ...symbol is also displayed Temperature Sensor Settings 28 Extern Sensor Temp Default Range OFF OFF t10 0 external temperature sensor 10 0 K at input 14 Select the temperature sensor that will be used b...

Страница 8: ...used to notify that service is required When activated Service and the symbol are displayed All control modes continue to function Airf The input is used to connect an air flow sensor When activated...

Страница 9: ...es 4 enter year Default Range Increment Selection 2010 2010 to 2099 1 Year Select the year 5 enter month Range Increment Selection 01 to 12 January to December 1 month Month Select the month 6 enter d...

Страница 10: ...event 1 cooling setpnt Default Range Increment Display 22 C 72 F 10 to 40 C 50 to 104 F Off 0 5 C 1 F MO Select the desired cooling temperature setpoint for the duration of Event 1 The minimum value i...

Страница 11: ...ontinue Event 1 4 Events Day If the 4 events per day option was selected at step 9 16 e1 Default Range Increment Display 06 00 00 00 to Monday Event 2 start time 15 minutes 15 minutes MO E1 Set the st...

Страница 12: ...t the desired heating temperature setpoint for the duration of Event 2 The maximum value is restricted by the cooling setpoint of Event 2 at step 20 Event 3 4 Events Day If the 4 events per day option...

Страница 13: ...copy Monday s schedule to Tuesday Wednesday Thursday and Friday 28 copy schedul Default Range No No Yes selected day If you do not want to copy a schedule select NO The currently configured days appea...

Страница 14: ...ked Yes No Select No to allow the user to change control modes Select Yes to lock the control mode to the user A lock symbol appears to indicate that the control mode is locked 32 quit Default Range Y...

Страница 15: ...the arrow keys while the temperature is displayed If the setpoint adjustment has been locked Step 29 on page 13 the lock symbol appears Room temperature Appears if setpoint adjustment is locked Change...

Страница 16: ...y on OFF Override Setpoint This function is only available if you have set the used time schedule option to Yes at Step 7 on page 9 When the schedule is triggered the thermostat uses the setpoints def...

Отзывы: