VAV Thermostat Controller
Specification and Installation Instructions
www.neptronic.com
Page | 5
TRIAC Output 1 (TO1)
8.
“Select TO1 Output Signal”
Default:
Range:
FLt (floating)
FLt (floating), OnOf (on/off), PULs (pulsed)
Select the desired signal from the available options.
If you select FLt, ramp TO1 will be used for TO2. TO1 ramp will be set to close and TO2 will be set to open.
If you select PULs, only the Heating 1 and Heating 2 ramps will be available at Step 9.
9.
“Select TO1 Signal Ramp”
Default:
Range:
Cr1 (Cooling ramp 1)
Cr1, Cr2, Hr1, Hr2, COr, OFF
Select the desired ramp from the available options.
If you selected FLt at Step 8, ramp TO1 will be used for TO2. TO1 ramp will be set to close and TO2 will be set to
open.
If you selected PULs at Step 8, only Heating Ramp 1 and Heating Ramp 2 will be available.
If you selected OnOf at Step
, or OFF at this step, go to Step 13.
Cooling Ramp 1
Cooling Ramp 2
Heating Ramp 1
Heating Ramp 2
Changeover Ramp
Off
10.
“Set Floating Time in Seconds”
Default:
Range:
Increment:
100 seconds
15 to 250 seconds
5 seconds
This option appears only if you selected
FLt
(Floating) at Step
8. Set the desired value for floating time signal.
11.
“Select Motor Direct Reverse”
Default:
Range:
Dir (Direct)
Dir (Direct) or Rev (Reverse)
Set the motor direction to either Direct (clockwise, 0 to 90°), or Reverse (counter clockwise, 90 to 0°).
Go to Step 16
12.
“Select TO1 Close Percent”
Default:
Range:
40% of demand
20%, 40%, 60%, 80%
This option appears if you selected
OnOf
at Step 8. Select the percentage at which you want TO1 to close (at % of demand of
the ramp selected at Step 9). Contact automatically opens at 0% of the demand.
TRIAC Output 2 (TO2)
13.
“Select TO2 Output Signal”
Default:
Range:
OnOf (on/off)
OnOf (on/off), PULs (pulsed)
Select the desired signal from the available options.
If you select PULs, only the Heating 1 and Heating 2 ramps will be available at Step 14.
14.
“Select TO2 Signal Ramp”
Default:
Range:
Cr1 (Cooling ramp 1)
Cr1, Cr2, Hr1, Hr2, COr, OFF
Select the desired ramp from the available options.
If you selected PULs at Step 13, only Heating Ramp 1 and Heating Ramp 2 will be available.