VAV Thermostat Controller
Specification and Installation Instructions
www.neptronic.com
Page | 6
If you selected PULs at Step 13, or OFF at this step, go to Step 16.
Cooling Ramp 1
Cooling Ramp 2
Heating Ramp 1
Heating Ramp 2
Changeover Ramp
Off
15.
“Select TO2 Close Percent”
Default:
Range:
40% of demand
20%, 40%, 60%, 80%
This option appears if you selected
OnOf
at Step 13. Select the percentage at which you want TO2 to close (at % of demand of
the ramp selected at Step 14). Contact automatically opens at 0% of the demand.
TRIAC Output 3 (TO3)
16.
“Select TO3 Output Signal”
Default:
Range:
OnOf (on/off)
FLt (floating), OnOf (on/off), PULs (pulsed)
Select the desired signal from the available options.
If you select FLt, ramp TO3 will be used for TO4. TO3 ramp will be set to close and TO4 will be set to open.
If you select PULs, only the Heating 1 and Heating 2 ramps will be available at Step 9.
17.
“Select TO3 Signal Ramp”
Default:
Range:
Hr1 (Heating ramp 1)
Cr1, Cr2, Hr1, Hr2, COr, OFF
Select the desired ramp from the available options.
If you selected FLt at Step 16, ramp TO1 will be used for TO2. TO1 ramp will be set to close and TO2 will be set to
open.
If you selected PULs at Step 16, only Heating Ramp 1 and Heating Ramp 2 will be available.
If
you selected OnOf at Step 16, go to Step 20.
If you selected PULs at Step 16, or OFF at this step, go to Step 21.
Cooling Ramp 1
Cooling Ramp 2
Heating Ramp 1
Heating Ramp 2
Changeover Ramp
Off
18.
“Set Floating Time in Seconds”
Default:
Range:
Increment:
100 seconds
15 to 250 seconds
5 seconds
This option appears only if you selected
FLt
(Floating) at Step
16. Set the desired value for floating time signal.
19.
“Select Motor Direct Reverse”
Default:
Range:
Dir (Direct)
Dir (Direct) or Rev (Reverse)
Set the motor direction to either Direct (clockwise, 0 to 90°), or Reverse (counter clockwise, 90 to 0°).
Go to Step 24
20.
“Select TO3 Close Percent”
Default:
Range:
40% of demand
20%, 40%, 60%, 80%
This option appears if you selected
OnOf
at Step 16. Select the percentage at which you want TO3 to close (at % of demand of
the ramp selected at Step 17). Contact automatically opens at 0% of the demand.