VAV Thermostat Controller
Specification and Installation Instructions
www.neptronic.com
Page | 10
38.
“Night Setback Heating Setpnt”
Default:
Range:
Increment:
16ºC
[61ºF]
10 to 40ºC
[50 to 104ºF]
0.5ºC
[1ºF]
This option appears if you’ve set one of the analog inputs to
nSb
(Night Setback contact) in Step 32, 33 or 34. Set the heating
setpoint that will be used
when the system is “Night Setback” Mode. The setpoint value is restricted by the “Night Setback
Cooling Setpnt” value (Step 39). The moon and heating symbols are also displayed.
39.
“Night Setback Cooling Setpnt”
Default:
Range:
Increment:
28ºC
[82ºF]
10 to 40ºC
[50 to 104ºF]
0.5ºC
[1ºF]
This option appears if you’ve set one of the analog inputs to
nSb
(Night Setback contact) in Step 32, 33 or 34. Set the cooling
setpoint that will be used when th
e system is “Night Setback” Mode. The setpoint value is restricted by the “Night Setback
etpnt” value (Step 38). The moon and heating symbols are also displayed.
40.
“Pressur Indepen Output”
Default:
Range:
FLt.1 (floating 1)
FLt.1, FLt.2, ANL.1, ANL.2
This option appears if you’ve set one of the analog inputs to either
PrSd
or
PrSa
(pressure sensor) in Step 32, 33 or 34. Select
which output is affected by pressure (connected to the actuator). These selections may vary based on options selected at Step
8 and 16.
Floating 1
(TO1 & TO2)
Floating 2
(TO3 & TO4)
Analog 1
(AO1)
Analog 2
(AO2)
41.
“Control Ramp CH Over”
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the changeover ramp. The cooling
and heating symbols are also displayed.
42.
“Control Ramp 1 Heating”
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the heating ramp 1. The heating symbol is also displayed.
43.
“Control Ramp 2 Heating”
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the heating ramp 2. The heating symbol is also displayed.
44.
“Control Ramp 1 Cooling”
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the cooling ramp 1. The cooling
symbol is also displayed.
45.
“Control Ramp 2 Cooling”
Default:
Range:
Increment:
2.0ºC
[4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC
[1ºF]
Select the desired proportional band value of the cooling ramp 2. The cooling
symbol is also displayed.