background image

 

VAV Thermostat Controller 

Specification and Installation Instructions 

 

TRO24T4XYZ1-Standard-180301-ESA.docx 

 

Page | 1

 

Model 

TRO24T4XYZ1  

Description 

The TRO24T4XYZ1 is a combination controller and thermostat. 
The VAV Thermostat Controller is designed for simple and 
accurate control of any variable air volume box in a number of 
zone control configurations. Its field configurable algorithms 
enable versatile implementation of required control sequences.   

Applications 

  Cooling only with or without terminal reheat 

  Heating/cooling with or without auto-changeover and 

terminal reheat 

  Pressure dependent or pressure independent 

  Single duct or dual duct 

  Serial or parallel fan power boxes (on/off or ECM) 

  Supply and exhaust applications  

  Auxiliary heating sources, such as electric baseboards, can 

also be applied 

Features 

  Backlit LCD with simple icon and text driven menus  

  Configurable inputs and outputs 

  Precise temperature control with programmable PI function 

  Selectable Fahrenheit or Celsius scale 

  Manual night setback override 

  Multi level lockable access menu and setpoint 

 

Selectable internal or external temperature sensor (10 KΩ) 

  Changeover by contact or external temperature sensor 

  Pressure sensor input with air flow program 

  Selectable proportional control band and dead band 

  Anti-freeze protection 

 

  

 

 

 

 

 

TRO24T4XYZ1  

Typical Application 

VAV applications incorporate a central unit that delivers a 
controlled volume of air, which can be cooled or heated, to 
multiple zones. Each zone incorporates a VAV control box with 
a motorized damper to adjust the flow of air to the controlled 
zone based on the demand. Some configurations include one or 
more of the following: air flow pressure sensor, fan, duct heater, 
duct temperature sensor, and auxiliary heat (e.g. baseboard).  
 

 

* Consult www.neptronic.com for details on these Neptronic products. 

Technical Specifications 

Description 

TRO24T4XYZ1  

Inputs 

3 Universal analog inputs: 0-10Vdc, Thermistor (10k Type 3), or digital input (dry contact) 
Available for sensors: external temperature, changeover, night setback or pressure 

Outputs

 

2 Analog outputs: 0-10Vdc or 2-10Vdc selectable (2mA max.) 
4 TRIAC outputs: on/off, pulse 0 or 24Vac (250 mA max.), or 2 floating outputs 

Power supply 

22 to 26Vac 50/60Hz 

Power consumption 

1VA 

Setpoint range 

10ºC to 40ºC [50ºF to 104ºF]  

External sensor range  

-40ºC to 100ºC [-40ºF to 212ºF] 

Control accuracy 

Temperature: ±0.4ºC [0.8ºF] 

Proportional band 

0.5ºC to 5ºC [1ºF to 10ºF] adjustable 

Electrical connection 

0.8 mm

[18 AWG] minimum 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95% non condensing 

Degree of protection of housing 

IP 30 (EN 60529) 

Weight 

160 g. [0.36 lb] 

Содержание TRO24T4XYZ1

Страница 1: ...roportional control band and dead band Anti freeze protection TRO24T4XYZ1 Typical Application VAV applications incorporate a central unit that delivers a controlled volume of air which can be cooled or heated to multiple zones Each zone incorporates a VAV control box with a motorized damper to adjust the flow of air to the controlled zone based on the demand Some configurations include one or more...

Страница 2: ...c 11 TRIAC output 4 TO4 12 Analog input 1 AI1 see step 32 and DIP switch DS2 1 2 13 Analog input 2 AI2 see step 33 and DIP switch DS2 3 4 14 Analog input 3 AI3 see step 34 and DIP switch DS2 5 6 15 Analog output 1 AO1 see step 24 16 Analog output 2 AO2 see step 25 Jumpers Jumpers Description JP1 Output Signal Selector TO3 and TO4 A B Internal TRIAC output signal is linked to internal 24 Vac same a...

Страница 3: ...odule on the base and secure using the screw Programming Mode The Mode Selector DIP switch DS1 must be set to the ON position Programming Mode Refer to Wiring on page 2 To exit set DIP switch back to the OFF position Operation Mode All changes will be saved Symbols used in this Manual Single Duct Temperature Heating Cooling TRIAC Output 1 TRIAC Output 2 TRIAC Output 3 TRIAC Output 4 Analog Output ...

Страница 4: ...nt to more than the value set as the maximum user point The maximum value is restricted by the minimum value set in Step 2 In other words the value that is set as the maximum cannot be less than the minimum value 4 User Setpnt Locked Default Range No Unlocked Yes No If set to No the user setpoint option is not locked and the user can adjust the desired setpoint temperature If set to Yes the user s...

Страница 5: ...ng Ramp 2 Changeover Ramp Off 10 Set Floating Time in Seconds Default Range Increment 100 seconds 15 to 250 seconds 5 seconds This option appears only if you selected FLt Floating at Step 8 Set the desired value for floating time signal 11 Select Motor Direct Reverse Default Range Dir Direct Dir Direct or Rev Reverse Set the motor direction to either Direct clockwise 0 to 90 or Reverse counter clo...

Страница 6: ...r1 Hr2 COr OFF Select the desired ramp from the available options If you selected FLt at Step 16 ramp TO1 will be used for TO2 TO1 ramp will be set to close and TO2 will be set to open If you selected PULs at Step 16 only Heating Ramp 1 and Heating Ramp 2 will be available If you selected OnOf at Step 16 go to Step 20 If you selected PULs at Step 16 or OFF at this step go to Step 21 Cooling Ramp 1...

Страница 7: ...g Ramp 1 Heating Ramp 2 Changeover Ramp Off 23 Select TO4 Close Percent Default Range 40 of demand 20 40 60 80 This option appears if you selected OnOf at Step 21 Select the percentage at which you want TO2 to close at of demand of the ramp selected at Step 22 Contact automatically opens at 0 of the demand Analog Outputs AO1 and AO2 24 Select AO1 Analog Ramp Default Range Cr1 Cooling ramp 1 Cr1 Cr...

Страница 8: ...cted by the maximum value Step 30 In other words the minimum value should be less than the maximum value 30 Max Vdc Analog AO2 Output Default Range Increment 10 0 Volts 0 0 to 10 0 Volts 0 1 Volt This option does not appear if the signal ramp for AO2 is set to OFF Step 25 Select the desired maximum voltage span value for the AO2 ramp The maximum value is restricted by the minimum value Step 29 In ...

Страница 9: ...ernal temperature sensor in Step 32 33 or 34 When the thermostat is connected to the appropriate analog input AI1 AI2 or AI3 the display shows the temperature read by the external temperature sensor Adjust the offset by comparing it with a known value e g thermometer If the sensor is not connected or short circuited the display is blank Error 36 CH Over SetPnt Temper Default Range Increment 24ºC 8...

Страница 10: ...nalog inputs to either PrSd or PrSa pressure sensor in Step 32 33 or 34 Select which output is affected by pressure connected to the actuator These selections may vary based on options selected at Step 8 and 16 Floating 1 TO1 TO2 Floating 2 TO3 TO4 Analog 1 AO1 Analog 2 AO2 41 Control Ramp CH Over Default Range Increment 2 0ºC 4ºF 0 5 to 5 0ºC 1 to 10ºF 0 5ºC 1ºF Select the desired proportional ba...

Страница 11: ...2 minutes 0 to 15 minutes 1 minute To protect the compressor set the delay in minutes before activating or reactivating the cooling contact 52 Adjust Intgral Time in Seconds Default Range Increment 0 seconds 0 to 250 seconds 5 seconds Set the desired value for the integration factor compensation 53 Enable Anti freeze Protect Default Range No disabled No Yes If this option is enabled heating starts...

Страница 12: ...Time in Seconds Default Range Increment 2 seconds 1 to 10 seconds 1 second This option appears if you have set one of the analog inputs to PrSd or PrSa in Step 32 33 or 34 Set the time in seconds of the numeric filter applied to the pressure analog input The numeric filter stabilizes the reading and slows down the answer of the system 57 air flow Intgral time in Seconds Default Range Increment 0 m...

Страница 13: ... balometer If you cannot stabilize the system you may need to increase the filter time value Step 56 65 Maximum Airflow Range Offset Increment 0 to K Factor or V nominal Max value 1 The thermostat displays the maximum airflow detected by the pressure sensor The thermostat will send a signal to the actuator to open the VAV box at maximum airflow When the value on thermostat is stable adjust the cal...

Страница 14: ...cess the Control Mode press the key The Control Mode appears for 5 seconds Press the key to scroll through the following control modes These options can vary depending on the options selected at Steps 6 and 7 on page 4 Auto Automatic Cooling or Heating Cooling only on Heating only on OFF Night Setback NSB This function is only available if you ve set one of the analog inputs to nSb Night Setback c...

Страница 15: ...Notes ...

Страница 16: ... need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Eastern time ...

Отзывы: