TM200/220/260/280FN 
RM200/220/260/280FN 

Specification & Installation Instruction

 

 

 

     

     

 

 

Enabling or disabling PWM mode 

1.  Remove power supply to actuator 
2.  Install jumper between pin 3 & 4 of J3  
3.  Select the desired action using the dipswitches (DS1): 

DS1-1 

DS1-2 

Action 

OFF 

ON 

Enable PWM Mode 

ON 

OFF 

Disable PWM Mode 

4.  Re-apply power supply to actuator 
5. 

Wait 5 seconds

  

6.  Remove power supply to actuator 
7.  Remove jumper between pin 3 & 4 of J3, re-install it between pin 4 & 5. 

8.

 

Re-apply power supply to actuator 

PWM is factory preset at 5 sec. pulse,

 

refer to programming section above to change pulse setting.

 

 

When not used for programming, 

jumper is placed between pin 4 & 5  

 
Zero and span calibration 

This feature is applicable to analog control signal only. 

1.  Remove power and put all dip switches "OFF". (factory preset). 

2.  Apply power and, 

within 10 seconds

 press and 

hold

 the reset button until the LED blinks once. 

The Zero and span calibration process then start. 

3.  Release the reset button. The LED is now constantly illuminated. 

4.  Apply new minimum voltage. 

It can be any value between 0 to 7 Vdc, with an external 0 to 10 volt supply (ex: MEP). 

5.  Press and release the reset button to memorize the new minimum voltage. The LED blinks. 

6.  Apply new maximum voltage. 

It can be any value between 3 to 10 Vdc, this value should be greater than the new minimum value. 

7.  Press and release the reset button to memorize the new maximum voltage. The LED blinks. 

The Zero and span calibration process is complete. 

 
Note: To reset zero and span to 2 to 10 Vdc (factory value). You just have to re-select the analog control signal mode, see 

Programming. 

 
Wiring Diagrams for auxiliary switches 

(on model 220 & 280)

 

 

 

Auxiliary switch rating:

  

5 Amp resistive, 250 Vac 

 

J

3

Pin #1

Pin #5

Pin #4

Pin #3

Pin #2

BLACK

RED

GREEN

BROWN

WHITE

BLUE

LOWER COMMON

LOWER CLOSED 10-90º

LOWER CLOSED 0-10º

UPPER COMMON

UPPER CLOSED 0-80º

UPPER CLOSED 80-90º