background image

TM200/220/260/280FN 
RM200/220/260/280FN 

Specification & Installation Instruction

 

 

 

 

ON

  1      2     3     4  

Rotation: CCW

Input in mA

Feedback in Vdc

Fail safe return at 90º

ON

  1      2     3     4   

Rotation: CW

Input in Vdc

Feedback in mA

Fail safe return at 0º

PC Board 

 

 

Dip switch settings 

 
 
 
 
 
 
 
 

 
 
 
 

 
Default Setting =  All dipswitches at OFF

 

 

 
Stroke adjustment 

 No control signal change 

1.  Apply power and, 

WAIT FOR LED TO BE OFF (around 10 seconds)

2.  Press and release the reset button to start the auto-stroke process. 

The LED should be illuminated. 

 

First option:

 

The actuator will then travel in both directions to find its limit and position itself according to the demand. 
The LED will extinguish, the process is complete. 

 

Second option:

 

When the desired start position is reached, press and release the reset button. The actuator will now go the end 
position. (you can also press and release the reset button when it reaches the end position)  
The LED will extinguish, the process is complete.

 

 
Programming 

 Change of control signal & PWM pulse setting 

1.  Remove power and put all dip switches "OFF". (factory preset). 

2.  Apply power and, 

within 10 seconds

, press and release the reset button. The LED should be blinking. 

3.  Select the control signal with dip switches: 

 

Digital or Analog Modes 

PWM Mode 

Move switch 

No1

 

"ON” and then “OFF”. 

Digital

 (On/Off or 3 point floating) 

5 sec. pulse (factory preset) 

Move switch 

No2

 

"ON” and then “OFF”. 

Analog

 (Default) 

25 sec. pulse 

4. 

Stroke adjustment

 

see the stroke adjustment section above.

 

Potentiometer

Dip switch

Reset button

LED

Clutch

1     2     3     4     5

TB1

ON

1  2  3  4 

DS1

PB1

LD1

J

3

Microcontroller

Terminal

TB5

1      2

N     L

Line voltage terminal

Pins for PWM selection

Transformer cut out 

Fuse