background image

 

High Pressure Atomiser Series 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 2 

 

 

BACnet Properties Configuration 

To establish communication on the network, and guarantee a unique ID of devices in a BACnet system, the following 
properties may have to be configured.  

Table 1 - BACnet Properties Configuration 

Property 

Default Value 

Configuration 

MAC Address 

000 

Set to a value between 000 and 127 via DIP switches. Can also be 
set to a value between 000 and 254 via menu. 
The values from 128-254 represent MS/TP non-token passing slave 
devices. 

Device Instance 

Auto 

 

The humidifier automatically configures its device instance to 
153,000 + MAC address.  

 

The value can be set manually via the menu. 

 

The value can be set manually through the 

WriteProperty

 

service to 

Device Object.Object_Identifier

.  

 

The device’s 

Object_Identifier

 is a combination of the 

Device 

Object_Type

 (8) and the 

Device_Instance

 (0-4194302), 

therefore its decimal or hexadecimal representation tends to be 
incomprehensible. 

 

For example, the 

Device_Instance

=1000 has an equivalent 

Object_Identifier

 of 0x020003E8 hexadecimal or 33555432 

decimal. 

Baud Rate 

0 = Auto 

 

The humidifier configures its baud rate automatically by detecting 
the network upon connection. 

 

The value can be set manually from the available values of Auto, 
9600, 19200, 38400, 76800. 

Max_Master 

127 

 

Configure 

Max_Master

 value to increase network efficiency when 

there are less than 127 devices on the network.  

 

The 

Max_Master

 value can be changed through the TRL to 

configure WriteProperty service to the Device 

Object.Max_Master

.   

For more information, refer to the

 

MAC Address and Max_Master

 

section.  

Device Object.Object_Name 

Name of the device 

 

Configure the name of the device through WriteProperty service 
to the 

Device Object.Object_Name

. For example, SKH. 

 

 

Содержание SKH Series

Страница 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Страница 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Страница 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Страница 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Страница 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Страница 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Страница 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Страница 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Страница 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Страница 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Страница 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Страница 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Страница 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Страница 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Страница 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Страница 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Страница 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Страница 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Страница 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Страница 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...

Страница 21: ...le and atomicReadFile FIL 4 PumpBootloaderUpdateFile File object for pump bootloader upgrade File_Size Archive Stream access method via atomicWriteFile and atomicReadFile PGM 1 FirmwareUpdateTask Firm...

Страница 22: ...Notes...

Страница 23: ......

Страница 24: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Отзывы: