High Pressure Atomiser Series 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 14 

 

ID 

Name 

Description 

W? 

Notes 

BV.8 

UVLampChangeDue 

Displays the status of the UV lamp change due. 

Read Only 

0 = Off, 1 = On 

Integrator - Alarms

 

BV.50 

AL_ServiceWarning 

Displays the status of the service warning. It indicates the 
upcoming cleaning for the humidifier. The warning is displayed 
when cleaning is due in 100 hours or less.  

Read Only 

0 = Off, 1 = On 

BV.51 

AL_ServiceAlarm 

Displays the status of the service alarm. The alarm is triggered 
when cleaning, UV lamp change or Silver Ion cartridge change is 
due. 

Read Only 

0 = Off, 1 = On 

BV.52 

AL_PumpGlobalAlarmMask 

Displays the status of the pump global alarm mask.  

Read Only 

0 = Off, 1 = On 

BV.56 

AL_GlobalPumpComTimeout 

Displays the status of the global pump communication timeout.  

Read Only 

0 = Off, 1 = On 

BV.57 

AL_GlobalZoneComTimeout 

Displays the status of the global zone communication timeout. 

Read Only 

0 = Off, 1 = On 

Advanced

 

BV.200 

PumpDrainValve 

Displays the status of pump drain valve. 

Read Only 

0 = Off, 1 = On 

BV.204 

PumpEnableVFD 

Displays the status of the pump enable VFD. 

Read Only 

0 = Off, 1 = On 

BV.210 

AL_PumpInletTempSensorFailure 

Displays the status of the pump inlet temperature sensor failure. 

Read Only 

0 = Off, 1 = On 

BV.214 

AL_PumpInletPressureSensorFailure 

Displays the status of the pump inlet pressure sensor failure. 

Read Only 

0 = Off, 1 = On 

BV.218 

AL_PumpOutputPressureSensorFailure  Displays the status of the pump output pressure sensor failure. 

Read Only 

0 = Off, 1 = On 

BV.222 

AL_PumpVFDFailure 

Displays the status of the pump VFD failure. 

Read Only 

0 = Off, 1 = On 

BV.226 

AL_PumpInletTempTooHigh 

Displays the status of the pump if the inlet water temperature of 
pump is above the maximum temperature. 

Read Only 

0 = Off, 1 = On 

BV.230 

AL_PumpInletTempTooLow 

Displays the status of the pump if the inlet water temperature of 
pump is below the minimum temperature. 

Read Only 

0 = Off, 1 = On 

BV.234 

AL_PumpInletPressureToLow 

Displays the status of the pump if the inlet pressure of pump is 
below the minimum pressure.  

Read Only 

0 = Off, 1 = On 

BV.238 

AL_PumpInletPressureToHigh 

Displays the status of the pump if the inlet pressure of pump is 
above the maximum pressure.  

Read Only 

0 = Off, 1 = On 

BV.242 

AL_PumpOutputPressureTooLow 

Displays the status of the pump if the output pressure of pump is 
below the minimum pressure.  

Read Only 

0 = Off, 1 = On 

BV.246 

AL_PumpOutputPressureTooHigh 

Displays the status of the pump if the output pressure of pump is 
above the maximum pressure. 

Read Only 

0 = Off, 1 = On 

BV.250 

AL_PumpTemperatureTooHigh 

Displays the status of the pump if the temperature of pump is 
above the maximum temperature.  

Read Only 

0 = Off, 1 = On 

BV.254 

AL_PumpServiceAlarm 

Displays whether the service alarm for the pump if currently 
enabled signifying the service due for the pump. 

Read Only 

0 = Off, 1 = On 

BV.258 

AL_PumpPressurizingTimeout 

Displays the status of the communication timeout for pressurizing 
of pump.  

Read Only 

0 = Off, 1 = On 

Содержание SKH Series

Страница 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Страница 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Страница 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Страница 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Страница 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Страница 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Страница 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Страница 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Страница 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Страница 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Страница 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Страница 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Страница 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Страница 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Страница 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Страница 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Страница 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Страница 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Страница 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Страница 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...