Introduction  

The SKH High Pressure Atomiser Humidifier BACnet

®

 Communication Module User Guide provides information about 

using the humidifier with BACnet communications feature. The BACnet communication protocol for building automation 
and control networks enables communication between client devices within a network. The humidifier provides a BACnet 
network interface between BACnet client devices and Neptronic Humidifier series devices. It uses the BACnet Master 
Slave/Token Passing (MS/TP) protocol at the BACnet MAC layer. 

Pre-requisites 

The BACnet communication user guide assumes that you are familiar with the concepts of BACnet and its terminology. 

Advantages of BACnet  

BACnet enabled humidifiers have the following advantages: 

 

Quick Message Transmission.

 The humidifier uses a synchronous implementation for BACnet messages making 

it quick and efficient. Each BACnet confirmed service request is answered as quickly as possible without using 
the 

Reply Postponed

 frame. The MS/TP implementation is performed within 

Tusage_delay

 of 15 minutes to 

ensure a 

Tusage_timeout

 value within 20 minutes.   

 

MS/TP  Support.

  The  humidifier  supports  a  Full  Master  Node  state  machine  for  MS/TP.  Max_Master  and  the 

instances are configured to the device object through 

BACnet WriteProperty

 service. The MAC address is set 

via the DIP switches. Programming mode determines the MS/TP baud rate setting of 9600, 19200, 38400, and 
76800. In the configuration mode, the device is configured through the device’s keypad. For more information 
about the WriteProperty, refer to 

Table 3 - Object Types Supported

. 

 

BIBB Support

. The humidifier functions the same way as the B-ASC type profile server and supports the specific 

BIBB as per their relevant definitions.  

o

 

DS-RP-B 

o

 

DS-RPM-B 

o

 

DS-WP-B 

o

 

DS-WPM-B 

o

 

DM-DCC-B 

o

 

DM-DDB-B 

o

 

DM-DOB-B 

o

 

DM-RD-B 

o

 

DM-TS-B 

o

 

DM-UTC-B 

o

 

DS-COV-B 

o

 

DS-COVP-B 

o

 

SCHED-WS-I-B 

 

Object Support

. The humidifier supports a fixed list of BACnet visible values, which appear as Present_Values 

of various BACnet standard object types in addition to a device object. For more information, refer t

Table 3 - 

Object Types Supported

 

 

Alarms

. The humidifier supports indication of various alarm conditions through value changes in properties of 

several objects. However, it does not generate BACnet event notifications.  

 

 

 

Содержание SKH Series

Страница 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Страница 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Страница 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Страница 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Страница 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Страница 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Страница 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Страница 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Страница 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Страница 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Страница 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Страница 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Страница 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Страница 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Страница 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Страница 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Страница 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Страница 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Страница 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Страница 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...

Страница 21: ...le and atomicReadFile FIL 4 PumpBootloaderUpdateFile File object for pump bootloader upgrade File_Size Archive Stream access method via atomicWriteFile and atomicReadFile PGM 1 FirmwareUpdateTask Firm...

Страница 22: ...Notes...

Страница 23: ......

Страница 24: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Отзывы: