High Pressure Atomiser Series 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 15 

 

ID 

Name 

Description 

W? 

Notes 

BV.262 

AL_PumpCoolingTimeout 

Displays the status of the communication timeout for the cooling of 
pump.  

Read Only 

0 = Off, 1 = On 

BV.266 

AL_PumpInvalidConfig 

Displays the status of configuration of the pump.  

Read Only 

0 = Off, 1 = On 

BV.270 

AL_PumpComTimeout 

Displays the status of the communication timeout of pump. It 
indicates that the communication delay is too long.  

Read Only 

0 = Off, 1 = On 

BV.274 

AL_Zone1ComTimeout 

Displays the status of communication timeout for the zone 1. It 
indicates that the communication delay is too long.   

Read Only 

0 = Off, 1 = On 

BV.275 

AL_Zone2ComTimeout 

Displays the status of communication timeout for the zone 2. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 = On 

BV.276 

AL_Zone3ComTimeout 

Displays the status of communication timeout for the zone 3. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 = On 

BV.277 

AL_Zone4ComTimeout 

Displays the status of communication timeout for the zone 4. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 = On 

BV.278 

AL_Zone5ComTimeout 

Displays the status of communication timeout for the zone 5. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 = On 

BV.279 

AL_Zone6ComTimeout 

Displays the status of communication timeout for the zone 6. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 = On 

BV.280 

AL_Zone7ComTimeout 

Displays the status of communication timeout for the zone 7. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 =On 

BV.281 

AL_Zone8ComTimeout 

Displays the status of communication timeout for the zone 8. It 
indicates that the communication delay is too long.  

Read Only 

0 = Off, 1 = On 

BV.282 

AL_Zone9ComTimeout 

Displays the status of communication timeout for the zone 9. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 = On 

BV.283 

AL_Zone10ComTimeout 

Displays the status of communication timeout for the zone 10. It 
indicates that the communication delay is too long. 

Read Only 

0 = Off, 1 = On 

SKH EZC 

ID 

Name 

Description 

W? 

Notes 

Integrator

 

BV.1 

SystemMode 

Displays the status of the system mode. 

Read Only 

0 = Off 1 = On 

BV.2 

ZoneMode 

Select whether to enable or disable the zone mode. 

Present Value 

0 = Off, 1 = On 

BV.3 

WaterPressure 

Displays the status of the water pressure. 

Read Only 

0 = Not Ready, 1 = Ready 

BV.4 

LimitedByDuctRH 

Displays the status of the duct relative humidity. 

Read Only 

0 = Off, 1 = On 

BV.30 

AL_GlobalAlarmMask 

Displays the status of the global alarm mask. 

Read Only 

0 = Off, 1 = On 

BV.31 

AL_DuctRHCutout 

Displays the status of the duct relative humidity cutout. 

Read Only 

0 = Off, 1 = On 

BV.32 

AL_AirflowCutout 

Displays the status of the airflow cutout. 

Read Only 

0 = Off, 1 = On 

BV.33 

AL_InterlockCutout 

Displays the status of the interlock cutout. 

Read Only 

0 = Off, 1 = On 

BV.34 

AL_NoCoordinator 

Displays the status of the communication between the master PCB 
and EZC. It indicates that the communication has been lost 
between EZC and SKH Master PCB alarm. 

Read Only 

0 = Off, 1 = On 

Содержание SKH Series

Страница 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Страница 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Страница 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Страница 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Страница 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Страница 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Страница 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Страница 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Страница 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Страница 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Страница 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Страница 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Страница 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Страница 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Страница 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Страница 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Страница 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Страница 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Страница 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Страница 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...

Страница 21: ...le and atomicReadFile FIL 4 PumpBootloaderUpdateFile File object for pump bootloader upgrade File_Size Archive Stream access method via atomicWriteFile and atomicReadFile PGM 1 FirmwareUpdateTask Firm...

Страница 22: ...Notes...

Страница 23: ......

Страница 24: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Отзывы: