High Pressure Atomiser Series
BACnet Communication Module User Guide
www.neptronic.com
Page | 15
ID
Name
Description
W?
Notes
BV.262
AL_PumpCoolingTimeout
Displays the status of the communication timeout for the cooling of
pump.
Read Only
0 = Off, 1 = On
BV.266
AL_PumpInvalidConfig
Displays the status of configuration of the pump.
Read Only
0 = Off, 1 = On
BV.270
AL_PumpComTimeout
Displays the status of the communication timeout of pump. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.274
AL_Zone1ComTimeout
Displays the status of communication timeout for the zone 1. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.275
AL_Zone2ComTimeout
Displays the status of communication timeout for the zone 2. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.276
AL_Zone3ComTimeout
Displays the status of communication timeout for the zone 3. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.277
AL_Zone4ComTimeout
Displays the status of communication timeout for the zone 4. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.278
AL_Zone5ComTimeout
Displays the status of communication timeout for the zone 5. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.279
AL_Zone6ComTimeout
Displays the status of communication timeout for the zone 6. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.280
AL_Zone7ComTimeout
Displays the status of communication timeout for the zone 7. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 =On
BV.281
AL_Zone8ComTimeout
Displays the status of communication timeout for the zone 8. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.282
AL_Zone9ComTimeout
Displays the status of communication timeout for the zone 9. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
BV.283
AL_Zone10ComTimeout
Displays the status of communication timeout for the zone 10. It
indicates that the communication delay is too long.
Read Only
0 = Off, 1 = On
SKH EZC
ID
Name
Description
W?
Notes
Integrator
BV.1
SystemMode
Displays the status of the system mode.
Read Only
0 = Off 1 = On
BV.2
ZoneMode
Select whether to enable or disable the zone mode.
Present Value
0 = Off, 1 = On
BV.3
WaterPressure
Displays the status of the water pressure.
Read Only
0 = Not Ready, 1 = Ready
BV.4
LimitedByDuctRH
Displays the status of the duct relative humidity.
Read Only
0 = Off, 1 = On
BV.30
AL_GlobalAlarmMask
Displays the status of the global alarm mask.
Read Only
0 = Off, 1 = On
BV.31
AL_DuctRHCutout
Displays the status of the duct relative humidity cutout.
Read Only
0 = Off, 1 = On
BV.32
AL_AirflowCutout
Displays the status of the airflow cutout.
Read Only
0 = Off, 1 = On
BV.33
AL_InterlockCutout
Displays the status of the interlock cutout.
Read Only
0 = Off, 1 = On
BV.34
AL_NoCoordinator
Displays the status of the communication between the master PCB
and EZC. It indicates that the communication has been lost
between EZC and SKH Master PCB alarm.
Read Only
0 = Off, 1 = On