EFCB Series Controller
Page | 7
EFCB Series Objects Table
The EFCB controllers use the following BACnet
®
object table. The
type
is the BACnet
®
Object type, the
instance
is the BACnet
®
Object. Together the
type
and
instance
form the BACnet
®
Object_Identifier for an object according to the following C-language algorithm:
object_identifier=(unsigned long)((unsigned long)
type
<<22)+
instance
ID
7
Name
Description
Writable
Property
E
F
C
B
12-GR
x
E
F
C
B
1x
E
F
C
B
1x-OE
1
E
F
C
B
1xQ
1
E
F
C
B
1xQ
1-OE
1
E
F
C
B
1xQ
2
E
F
C
B
1xQ
2-OE
1
E
F
C
B
1xQ
3
E
F
C
B
1xQ
4
E
F
C
B
1xQ
4-OE
1
Notes
AI.1
Intern.Temper.
Internal temperature sensor value
Out of service
x x x x x x
x x
x x
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AI.2
Extern.Temper.
External temperature sensor value
Out of service
x
x
x
x
x
x
x
x
x
x
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AI.3
ChangeOverTemper.
Changeover temperature sensor value
Out of service
x x x x x x
x x
x x
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AI.4
Intern.Humidity
8
Internal humidity sensor value
Out of service
x
x
x
x
x
x
x
x
x
5-95%RH, Resolution 0.1%RH
AI.9
Extern.Humidity
9
External humidity sensor value
Out of service
x x x x x
x x
x x
5-95%RH, Resolution 0.1%RH
AI.13
AnalogInput3
10
Analog input 3, mode selected by dipswitch on
EFCB
Out of service
x x x x x x
x x
x x
If BV.6 is set to “Intern.Sensor” and/or MSV.4 = “10k”
0-10Volt or -40-100ºC or -40-212ºF, Resolution
0.01Volt or 0.01ºC/0.02ºF
If BV.6 is set to “Extern.Sensor” and MSV.4
≠
“10k”
AV.99 to AV.100, Resolution 0.01ºC/0.02ºF
AI.14
AnalogInput4
11
Analog input 4, mode selected by dipswitch on
EFCB
Out of service
x x x x x x
x x
x x
0-10Volt or -40-100ºC or -40-212ºF, Resolution
0.01Volt or 0.01ºC/0.02ºF
AI.15
AnalogInput5
12
Analog input 5, mode selected by dipswitch on
EFCB
Out of service
x x x x x x
x x
x x
0-10Volt or -40-100ºC or -40-212ºF, Resolution
0.01Volt or 0.01ºC/0.02ºF
AI.16
AnalogInput6
13
Analog input 6, mode selected by dipswitch on
EFCB
Out of service
x x x x x x
x x
x x
0-10Volt or -40-100ºC or -40-212ºF, Resolution
0.01Volt or 0.01ºC/0.02ºF
AV.1
ControlTemper.
Temperature reading
Out of service
x x x x x x
x x
x x
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AV.2
HeatingDemand Heating
demand
x
x
x
x
x
x
x
x
x
x
0-100%, Resolution 0.1%
AV.3
CoolingDemand Cooling
demand
x x x x x x
x x
x x
0-100%, Resolution 0.1%
AV.4
FanDemand Fan
demand
x
x
x
x
x
x
x
x
x
x
0-100%, Resolution 0.1%
AV.5
Intern.Temper.Offset
Internal temperature offset calibration
Present Value
x x x x x x
x x
x x
±5.0ºC, Resolution 0.1ºC
AV.6
Extern.Temper.Offset
External temperature offset calibration
Present Value
x x x x x x
x x
x x
±5.0ºC, Resolution 0.1ºC
AV.7
Temper.SetPointOcc
Temperature set point
Present Value
x x x x x x
x x
x x
AV.8 to AV.9, Resolution 0.5ºC/1ºF
7
ID is equal to ObjectType.Instance
8
Internal sensor is available when a compatible controller is connected with a TFLH-INT; otherwise object is always out of service.
9
External sensor is available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.
10
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
11
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
12
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
13
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
Содержание EFCB Series
Страница 2: ......