![Neptronic EFCB Series Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/neptronic/efcb-series/efcb-series_user-manual_1667974017.webp)
EFCB Series Controller
Page | 15
ID
7
Name
Description
Writable
Property
EF
CB
12
-G
Rx
EF
CB
1x
EF
CB
1x
-O
E1
EF
CB
1x
Q1
EF
CB
1x
Q1-
O
E
1
EF
CB
1x
Q2
EF
CB
1x
Q2-
O
E
1
EF
CB
1x
Q3
EF
CB
1x
Q4
EF
CB
1x
Q4-
O
E
1
Notes
MSV.18
TO1Signal
Ramp that control TRIAC output 1
Present Value
x x x x x
x x
x x
1= Off
2= ChangeOverWithFan
3= CoolingWithFan
4= HeatingWithFan
5= Loc.HeatWithFan
6= Loc.Heat
MSV.19
TO2Signal
Ramp that control TRIAC output 2
Present Value
x x x x x
x x
x x
1= Off
2= ChangeOverWithFan
3= CoolingWithFan
4= HeatingWithFan
5= Loc.HeatWithFan
6= Loc.Heat
MSV.20
TO3Signal
Ramp that control TRIAC output 3
Present Value
x x x x x
x x
x x
1= Off
2= ChangeOverWithFan
3= CoolingWithFan
4= HeatingWithFan
5= Loc.HeatWithFan
6= Loc.Heat
MSV.22
TO1Mode
Signal output configuration for TRIAC output 1
Present Value
x x x x x
x x
x x
States available if MSV.18 is set to “HeatingWithFan”
or “ReheatWithFan” or “Reheat”
1= Pulsing
2= On_Off
3= Floating
States available if MSV.18 is set to
“ChangeOverWithFan” or “CoolingWithFan”
1= On_Off
2= Floating
States available if MSV.18 is set to “Off”
1= On_Off
MSV.23
TO2Mode
Signal output configuration for TRIAC output 2
Present Value
x x x x x
x x
x x
States available if MSV.22 is set to “Floating”
1= Floating
States available if MSV.22 is other then “Floating” and
MSV.19 is set to “HeatingWithFan” or
“ReheatWithFan” or “Reheat”
1= Pulsing
2= On_Off
States available if MSV.19 is set to
“ChangeOverWithFan” or “CoolingWithFan”
1= On_Off
2= Floating
Содержание EFCB Series