EFCB Series Controller
Page | 8
ID
7
Name
Description
Writable
Property
EF
CB
12
-G
Rx
EF
CB
1x
EF
CB
1x
-O
E1
EF
CB
1x
Q1
EF
CB
1x
Q1-
O
E
1
EF
CB
1x
Q2
EF
CB
1x
Q2-
O
E
1
EF
CB
1x
Q3
EF
CB
1x
Q4
EF
CB
1x
Q4-
O
E
1
Notes
AV.8
Min.SetPointOcc
Minimum temperature set point allowed
Present Value
x x x x x x
x x
x x
0 to AV.9 , Resolution 0.5ºC/1ºF
AV.9
Max.SetPointOcc
Maximum temperature set point allowed
Present Value
x x x x x x
x x
x x
AV.8 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF
AV.10
SetPointCoolNoOcc.
No occupancy cooling set point
Present Value
x x x x x x
x x
x x
AV.11 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF
AV.11
SetPointHeatNoOcc.
No occupancy heating set point
Present Value
x x x x x x
x x
x x
10.0ºC or 50ºF to AV.10, Resolution 0.5ºC/1ºF
AV.12
CoolingProp.Band1
Proportional band for cooling
Present Value
x
x
x
x
x
x
x
x
x
x
0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF
AV.13
HeatingProp.Band1
Proportional band for heating
Present Value
x x x x x x
x x
x x
0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF
AV.14
CoolingDeadBand1
Dead band for cooling
Present Value
x
x
x
x
x
x
x
x
x
x
0-5ºC or 0-10ºF, Resolution 0.1ºC/0.2ºF
AV.15
HeatingDeadBand1
Dead band for heating
Present Value
x x x x x x
x x
x x
0-5ºC or 0-10ºF, Resolution 0.1ºC/0.2ºF
AV.16
FanTimeOutDelay
Fan shutoff delay when there is no demand
Present Value
x x x x x x
x x
x x
0-255 seconds, resolution Resolution 1 second
AV.23
ChangeOverSetPoint
Changeover set point
Present Value
x x x x x x
x x
x x
10-40ºC or 50-104ºF, Resolution 0.5ºC/1ºF
AV.24
NightSetBackDelay
Override delay when in night
Present Value
x x x x x
x x
x x
0-180 minutes, Resolution 15 minutes
AV.25
FanDampingFactor
Slow the effect on the fan of change of demand
Present Value
x
x
x
x
x
x
x
x
x
x
0-255 seconds, Resolution 1 second
AV.26
Int.TimeFactorHeating
Heating integral time factor
Present Value
x x x x x x
x x
x x
0-250 seconds, Resolution 5 seconds
AV.27
CoolingAntiCycleDelay
Cooling start will be delayed by this value
Present Value
x
x
x
x
x
x
x
x
x
x
0-15 minutes, Resolution 1 minute
AV.28
Loc.Heat.Demand Local
reheat
demand
x x x x x x
x x
x x
0-100%
AV.29
Loc.Heat.Prop.Band
Proportional band for local reheat
Present Value
x x x x x x
x x
x x
0.5-5.0ºC or 1-10ºF, Resolution 0.5ºC/1ºF
AV.30
Loc.Heat.DeadBand
Dead band for local reheat
Present Value
x x x x x x
x x
x x
0-5ºC or 0-10ºF, Resolution 0.1ºC/0.2ºF
AV.31
FloatingMotorTiming Floating
time
Present
Value
x x x x x
x x
x x
15-250 seconds
AV.36
Dehumid.Demand
14
Dehumidification
demand
x
x
x
x
x
x
x
x
x
0-100%
AV.37
HumiditySetPoint
15
Humidification/Dehumidification set point
Present Value
x x x x x
x x
x x
10.0-65.0%RH, Resolution 0.5%RH
AV.38
Intern.HumidityOffset
16
Internal humidity sensor offset
Present Value
x
x
x
x
x
x
x
x
x
±5.0%RH, Resolution 0.1%RH
AV.39
NoOcc.OverrideDelay
Override delay when in no occupancy
Present Value
x x x x x x
x x
x x
0-180 minutes, Resolution 15 minutes
AV.40
HumidityControlRamp
17
Humidification/Dehumidification proportional band
Present Value
x
x
x
x
x
x
x
x
x
0.5-5.0%RH, Resolution 0.5%RH
AV.41
Humidif.Demand
18
Humidification
demand
x x x x x
x x
x x
0-100%
AV.45
Extern.HumidityOffset
19
External humidity sensor offset
Present Value
x x x x x
x x
x x
±5.0%RH, Resolution 0.1%RH
AV.49
ChangeOverDemand Changeover
demand
x x x x x x
x x
x x
0-100%, Resolution 0.1%
AV.50
ChangeOverProp.Band
Proportional band for changeover
Present Value
x x x x x x
x x
x x
0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF
AV.51
ChangeOverDeadBand
Dead band for changeover
Present Value
x
x
x
x
x
x
x
x
x
x
0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF
AV.52
AnalogOutput1Min.
Minimum voltage of analog output 1
Present Value
x x x x x x
x x
x x
0 Volt to AV.54, Resolution 0.1 Volt
AV.53
AnalogOutput2Min.
Minimum voltage of analog output 2
Present Value
x
x
x
x
x
x
x
x
x
x
0 Volt to AV.55, Resolution 0.1 Volt
AV.54
AnalogOutput1Max.
Maximum voltage of analog output 1
Present Value
x x x x x x
x x
x x
AV.52 to 10.0 Volt, Resolution 0.1 Volt
AV.55
AnalogOutput2Max.
Maximum voltage of analog output 2
Present Value
x x x x x x
x x
x x
AV.53 to 10.0 Volt, Resolution 0.1 Volt
14
Available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.
15
Available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.
16
Internal sensor is available when a compatible controller is connected with a TFLH-INT; otherwise object is always out of service.
17
Available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.
18
Available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.
19
External sensor is available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.