EFCB Series Controller
Page | 16
ID
7
Name
Description
Writable
Property
EF
CB
12
-G
Rx
EF
CB
1x
EF
CB
1x
-O
E1
EF
CB
1x
Q1
EF
CB
1x
Q1-
O
E
1
EF
CB
1x
Q2
EF
CB
1x
Q2-
O
E
1
EF
CB
1x
Q3
EF
CB
1x
Q4
EF
CB
1x
Q4-
O
E
1
Notes
States available if MSV.19 is set to “Off”
1= On_Off
MSV.24
TO3Mode
Signal output configuration for TRIAC output 2
Present Value
x x x x x
x x
x x
States available if MSV.20 is set to “HeatingWithFan”
or “ReheatWithFan” or “Reheat”
1= Pulsing
2= On_Off
States available if MSV.20 is set to
“ChangeOverWithFan” or “CoolingWithFan” or “Off”
1= On_Off
MSV.33
ChangeOverControlMode
48
Changeover selected control mode status
Present Value
x x x x x x
x x
x x
1= Locally
2= Cooling
3= Heating
MSV.34
ExternTemper.Type
Select external temperature sensor type
49
Present
Value
x
1=10k (link to hardware ai.1)
2=2-10V (link to hardware ai.3)
3=0-10V (link to hardware ai.3)
MSV.35
HumidityControlMode
50
Selected humidity control mode (in programming
mode)
Present Value
x x x x x
x x
x x
1= Auto
2= Dehumidification
3= Humidification
4= Off
MSV.36
Extern.HumidityInput
51
External humidity sensor analog input. Analog input
selected should be in 0-10V (HW dipswitch
selection).
Present Value
x x x x x
x x
x x
1= Off
2= AnalogInput3
3= AnalogInput4
4= AnalogInput5
5= AnalogInput6
MSV.50
Contact1Signal
Ramp that control digital output 1
Present Value
x x x x
x x
x x
1= Off
2= ChangeOverWithFan
3= CoolingWithFan
4= HeatingWithFan
5= Loc.HeatWithFan
6= Loc.Heat
7= HumidiWithFan (only when connected with a TFLH-
EXT or a TFLH-INT | not available with GRx)
48
Locally mode lets the thermostat manage the cooling or heating status for change over ramp. The other 2 statuses force the thermostat into a specific state.
49
Only in version 1.12 and above.
50
Available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.
51
If both sensor (internal and external) are available, selecting an analog input will not affect “HumidityControlSource”, you must set BV.8 = 1 to use external humidity sensor as control source. Available when a
compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.