BM000/020/060(F)(FF)N
Specification & Installation Instruction
4
Zero and span calibration
This feature is applicable to analog control signal only.
1. Remove power and put all dip switches "OFF". (factory preset).
2. Apply power and,
within 10 seconds
press and
hold
the reset button until the LED blinks once.
The Zero and span calibration process then start.
3. Release the reset button. The LED is now constantly illuminated.
4. Apply new minimum voltage.
It can be any value between 0 to 7 Vdc, with an external 0 to 10 volt supply (ex: MEP).
5. Press and release the reset button to memorize the new minimum voltage. The LED blinks.
6. Apply new maximum voltage.
It can be any value between 3 to 10 Vdc, this value should be greater than the new minimum value.
7. Press and release the reset button to memorize the new maximum voltage. The LED blinks.
The Zero and span calibration process is complete.
Note: To reset zero and span to 2 to 10 Vdc (default setting). You just have to re-select the analog control signal mode, see
Programming.
Wiring Diagrams for auxiliary switches
(on model 020)
Auxiliary switch rating:
5 Amp resistive, 250 Vac
BLACK
RED
GREEN
BROWN
WHITE
BLUE
LOWER COMMON
LOWER CLOSED 10-90º
LOWER CLOSED 0-10º
UPPER COMMON
UPPER CLOSED 0-80º
UPPER CLOSED 80-90º