background image

BM000/020/060(F)(FF)N 

Specification & Installation Instruction

 

 

 

 

ON

  1      2     3     4  

Rotation: CCW

Input in mA

Feedback in Vdc

Fail safe return at 90º

ON

  1      2     3     4   

Rotation: CW

Input in Vdc

Feedback in mA

Fail safe return at 0º

PC Board 

 

Dip switch settings 
 
 
 
 
 

 

 
 
 
 
 

 

 
 
 
 
 

Default Setting =  All dipswitches at OFF

 

 

Stroke adjustment 

 No control signal change 

1.  Apply power and, 

WAIT FOR LED TO BE OFF (around 10 seconds)

2.  Press and release the reset button to start the auto-stroke process. 

The LED should be illuminated. 

 

First option:

 

The actuator will then travel in both directions to find its limit and position itself according to the demand. 
The LED will extinguish, the process is complete. 

 

Second option:

 

When the desired start position is reached, press and release the reset button. The actuator will now go the end 
position. (you can also press and release the reset button when It's reaches the end position)  
The LED will extinguish, the process is complete.

 

 

Programming 

 Change of control signal & PWM pulse setting 

1.  Remove power and put all dip switches "OFF" (default setting). 

2.  Apply power and, 

within 10 seconds

, press and release the reset button. The LED should be blinking. 

3.  Select the control signal with dip switches: 

 

Digital or Analog Modes 

PWM Mode 

Move switch 

No1

 

"ON” and then “OFF”. 

Digital

 (On/Off or 3 point floating) 

5 sec. pulse (default setting) 

Move switch 

No2

 

"ON” and then “OFF”. 

Analog

 (Default) 

25 sec. pulse 

Stroke adjustment

 

see the stroke adjustment section above.

 

 

Enabling or disabling PWM mode 

1.  Remove power supply to actuator 
2.  Install jumper between pin 3 & 4 of JP7  
3.  Select the desired action using the dipswitches (DS1): 

DS1-1 

DS1-2 

Action 

OFF 

ON 

Enable PWM Mode 

ON 

OFF 

Disable PWM Mode 

4.  Re-apply power supply to actuator 
5. 

Wait 5 seconds

  

6.  Remove power supply to actuator 
7.  Remove jumper between pin 3 & 4 of JP7, re-install it between pin 4 & 5. 

8. 

Re-apply power supply to actuator 

PWM is factory preset at 5 sec. pulse, 
refer to programming section above to change pulse setting.

 

 

When not used for programming, 

jumper is placed between pin 4 & 5  

 

BM060N/GMR

1     2     3     4     5

ON

1  2  3  4

J

P

7

Microcontroller

Pins for PWM selection

Reset button

Dip switch

LED

Terminal

J

P

7

Pin #1

Pin #5

Pin #2

Pin #3

Pin #4

Содержание BM000N

Страница 1: ... 90 degrees mechanically adjustable default setting 90º stroke Direction of rotation Reversible Clockwise CW or Counterclockwise CCW default setting CW direction Ambient temperature 22ºF to 122ºF 30º C to 50º C Storage temperature 22ºF to 122ºF 30º C to 50º C Relative Humidity 5 to 95 non condensing Weight 3 lbs 1 4 kg Warning Do not press the clutch when actuator is powered Dimensions Dimension I...

Страница 2: ...ntrol In this mode the actuator is sensitive to induced electrical voltages from external sources To prevent such interference if the signal on pins 4 and 3 on TB1 are from an external 24 Vac source install a resistor 2 2kohm 0 5W between pins 4 and 1 and another of 2 2kohms 0 5W between pins 3 and 1 of TB1 These resistors are included Input Signal and Feedback setup Input Signal Feedback Analog M...

Страница 3: ...g 1 Remove power and put all dip switches OFF default setting 2 Apply power and within 10 seconds press and release the reset button The LED should be blinking 3 Select the control signal with dip switches Digital or Analog Modes PWM Mode Move switch No1 ON and then OFF Digital On Off or 3 point floating 5 sec pulse default setting Move switch No2 ON and then OFF Analog Default 25 sec pulse Stroke...

Страница 4: ...EP 5 Press and release the reset button to memorize the new minimum voltage The LED blinks 6 Apply new maximum voltage It can be any value between 3 to 10 Vdc this value should be greater than the new minimum value 7 Press and release the reset button to memorize the new maximum voltage The LED blinks The Zero and span calibration process is complete Note To reset zero and span to 2 to 10 Vdc defa...