BM000/020/060(F)(FF)N 

Specification & Installation Instruction

 

 

 

 

Mechanical Installation

 

 

1. 

Manually  close  the  damper  blades  and  positioned  the 
actuator at 0º or 90º.

 

2. 

Slide the actuator onto the shaft. 

 

3. 

Tighten  the  nuts  on  the  “U”  bolt  to  the  shaft  with  a  8mm 
wrench to a torque of 60 in.lb. [6,7 Nm].

 

4. 

Slide the mounting bracket under the actuator. Ensure free 
movement  of  the  slot  at  the  base  of  the  actuator.  The 
bracket pin must be placed in the mid distance of the slot.

 

5. 

Fix the bracket to the ductwork with #8 self-tapping screws.

 

 

Wiring Diagrams 
Analog or PWM

 

 

 

 

Digital signal  

Digital 

 3 wire / 2 position 

 

Digital 

 4 wire / 3 point floating 

 

Special consideration for Digital control 

In this mode, the actuator is sensitive to induced electrical voltages 

from external sources

. To prevent such interference, if the signal on pins 4 and 3 

on TB1 are from an 

external 24 Vac source

, install a resistor 2.2kohm, 0.5W between pins 4 and 1 and another of 2.2kohms, 0.5W between pins 3 

and 1 of TB1. These resistors are included.

 

 

Input Signal and Feedback setup 
 

Input Signal 

Feedback 

Analog Mode 

Input Signal is set with Dipswitch # 3 

DS1-3 at OFF = 2 

– 10Vdc (default setting) 

DS1-3 at ON = 4 

– 20mA 

Feedback is set with Dipswitch #4 

DS1-4 at OFF = 4 

– 20mA (default setting) 

DS1-4 at ON = 2 

– 10Vdc 

Digital & PWM

 

Mode 

 

No Input Signal Setting  

 

 

DS1-3 MUST be at OFF 

 

 

CLUTCH

MOUNTING
BRACKET

1

2

3

4

5

COMMON (-)

TB1

24 Vac or 30 Vdc (+)

INPUT SIGNAL

FEEDBACK

24 Vac (+)

2.2 K

2.2 K

1

2

3

4

5

FEEDBACK

DRIVE CCW

TB1

COMMON (-)

DRIVE CW

2.2 K

2.2 K

1

2

3

4

5

FEEDBACK

DRIVE CCW

COMMON (-)

24 VAC (+)

TB1

DRIVE CW

!

Содержание BM000N

Страница 1: ... 90 degrees mechanically adjustable default setting 90º stroke Direction of rotation Reversible Clockwise CW or Counterclockwise CCW default setting CW direction Ambient temperature 22ºF to 122ºF 30º C to 50º C Storage temperature 22ºF to 122ºF 30º C to 50º C Relative Humidity 5 to 95 non condensing Weight 3 lbs 1 4 kg Warning Do not press the clutch when actuator is powered Dimensions Dimension I...

Страница 2: ...ntrol In this mode the actuator is sensitive to induced electrical voltages from external sources To prevent such interference if the signal on pins 4 and 3 on TB1 are from an external 24 Vac source install a resistor 2 2kohm 0 5W between pins 4 and 1 and another of 2 2kohms 0 5W between pins 3 and 1 of TB1 These resistors are included Input Signal and Feedback setup Input Signal Feedback Analog M...

Страница 3: ...g 1 Remove power and put all dip switches OFF default setting 2 Apply power and within 10 seconds press and release the reset button The LED should be blinking 3 Select the control signal with dip switches Digital or Analog Modes PWM Mode Move switch No1 ON and then OFF Digital On Off or 3 point floating 5 sec pulse default setting Move switch No2 ON and then OFF Analog Default 25 sec pulse Stroke...

Страница 4: ...EP 5 Press and release the reset button to memorize the new minimum voltage The LED blinks 6 Apply new maximum voltage It can be any value between 3 to 10 Vdc this value should be greater than the new minimum value 7 Press and release the reset button to memorize the new maximum voltage The LED blinks The Zero and span calibration process is complete Note To reset zero and span to 2 to 10 Vdc defa...

Отзывы: