GATE ALARM DELAY TIME
1 0 _ _ * #
Sets the gate alarm delay time
m = minutes, s = x10 seconds
Programmable range is
1001*#
(10s) to
1041*#
(4min:10s)
Factory default value is
1010*#
(1min:0s)
The gate alarm will only sound once the gate has remained open for longer than the GATE
ALARM DELAY time. The GATE ALARM INSTANT user code can be used to temporarily
override this delay period, and the GATE ALARM BYPASS user code can be used to
temporarily disable the gate alarm function.
GATE CHIME ON CLOSE
1 1 9 _ * #
Enable or disable a gate close chime, only when gate chiming is enabled.
? = 0 (no chime on close) or 1 (chime on close)
Factory default value is
1190*#
(no chime on close)
The user can enable a gate chime notification using the GATE CHIME user code, as
detailed in the Druid LCD User Manual. This GATE CHIME ON CLOSE installer code
additionally enables chiming on closure of the gate as well.
INPUT TOGGLE SELECT
1 1 1 _ * #
Selects toggling or direct on/off control of the fence.
? = 0 (direct control) or 1 (toggle control)
Factory default value is
1110*#
(direct control)
With direct control, the fence is energized when the input transitions to open circuit.
With toggle control, the fence operating state is toggled each time the input transitions
from closed to open circuit.
FENCE CONDITION CHECK LEVEL
2 0 1 _ * #
Sets the value at which the CHECK message will be displayed should the fence condition
indicator reduce to or below this set value.
? = check level between 3 and 6
Programmable range is
2013*#
(3 = fair to poor) to
2016*#
(6 = good)
Factory default value is
2014*#
(4 = fair)
*Can be directed to a specific zone, using KEYPAD ZONE FOCUS.
Programmable options
20
m s
?
?
?