EXPANSION CARD CONFIGURATION
5 0 2 _ * #
Selects the configuration used in assigning a function to each of the ten relays and each of
the four inputs on the expansion card.
? = configuration to select (contact NEMTEK for customized configurations)
Programmable range is
5020*#
to
5022*#
Factory default value is
5020*#
(Configuration 0)
The expansion card address jumper must be set to 1 for the master unit’s information or 2 for the
slave unit’s information.
Configuration 0.
Relay 1 = Expansion card communication timeout.
Relay 6 = Mains fail.
Relay 2 = Zone 1 On/Off status.
Relay 7 = Battery low or Service alarm.
Relay 3 = Zone 2 On/Off status.
Relay 8 = Zone 1 in “Check”.
Relay 4 = No Function.
Relay 9 = Zone 2 in “Check”.
Relay 5 = No Function.
Relay10 = Unit tamper state.
Input 1 = Zone 1 On / Off control.
Input 3 = No Function.
Input 2 = Zone 2 On / Off control.
Input 4 = No Function.
Configuration 1.
Relay 1 = Expansion card communication timeout.
Relay 6 = Zone 1 in “Check”.
Relay 2 = Zone 1 On/Off status.
Relay 7 = Zone 2 in “Check”.
Relay 3 = Zone 2 On/Off status.
Relay 8 = Mains fail, battery low, service, tamper.
Relay 4 = No Function.
Relay 9 = Zone 1 in alarm.
Relay 5 = No Function.
Relay10 = Zone 2 in alarm.
Input 1 = Zone 1 On / Off control.
Input 3 = No Function.
Input 2 = Zone 2 On / Off control.
Input 4 = No Function.
Configuration 2.
Relay 1 = Expansion card communication timeout.
Relay 6 = Mains fail.
Relay 2 = Zone 1 On/Off status.
Relay 7 = Battery low, service alarm.
Relay 3 = Zone 2 On/Off status.
Relay 8 = No Function.
Relay 4 = No Function.
Relay 9 = No Function.
Relay 5 = No Function.
Relay10 = Tamper.
Input 1 = No Function.
Input 3 = No Function.
Input 2 = No Function.
Input 4 = No Function.
LARGE NETWORK TOPOLOGY
5 0 4 _ * #
Switches the large network topology from daisy chain to multi drop.
? = 0 (Daisy chain) or 1 (Multi drop)
Factory default value is
5040*#
(Daisy chain)
See the “D24 RS485 Network card” manual for further information on network topologies.
Programmable options
27
?