SOLAR POWERED INSTALLATION
4 0 7 _ * #
Modifies the unit operation for permanent battery operation.
? = 0 (disabled, requires mains power) or 1 (solar installation)
Factory default value is
4070*#
(disabled)
If the unit is to be run permanently from battery power, which is typically the case when running a
solar powered site, then enabling this function will prevent the unit from reacting to mains power
loss as an error condition.
MAINS FAIL CHIME
4 0 9 _ * #
Enable or disable mains fail chime.
? = 0 (no chime on mains fail) or 1 (chime on mains fail)
Factory default value is
4091*#
(chime on mains fail)
The unit and connected keypad will chime upon detecting mains failure, if enabled.
DEACTIVATION ON COMMS LOSS
4 8 0 _ * #
Enable or disable whether the unit deactivates fence monitoring when communication is
lost.
? = 0 (Deactivation disabled) or 1 (Deactivation enabled)
Factory default value is
4800*#
(Deactivation disabled)
When enabled, the unit will deactivate the fence monitoring when no network communication is
present for longer than 60 seconds on the data port. The deactivation only happens once after a
communication loss and the function is reset on each successful communication restoration.
Therefore, after a communication loss deactivation event, if the unit is manually activated again
using the keypad, mag switch or digital input, it will then not deactivate again while communication
remains lost.
The communication would have to be restored and then lost again (for more than 60s) for the unit
to then self-deactivate again.
SLAVE UNIT PRESENT
5 0 0 _ * #
Enable or disable whether a slave unit should be present.
? = 0 (Master only 2-zone system) or 1 (Slave connected 4-zone system)
Factory default value is
5000*#
(Master only 2-zone installation)
The master unit needs to be configured as to whether a slave unit is connected, creating a four-
zone system, or if it is a master only two-zone system. This is required so that a communication
failure (service alarm) can be generated should the slave not respond to the master’s request for
information, and so that the keypad can be dealt with correctly as either a two- or four-zone
installation.
26
?
?
?
Programmable options
?