Z2 ON/OFF INPUT FUNCTION
1 1 3 _ * #
Sets the functionality of the Z2 On/Off input.
? = 0 (On/Off), 1 (panic), 2 (lock Z2 in an inactive state if input is open i.e. safety
lockout)
Factory default value is
1130
*
#
(On/Off)
FENCE STATE AT POWER ON
2 0 2 _ * #
Sets the operating state that the fence is returned to after a complete power failure has
ended.
? = 0 (off), 1 (on) or 2 (fence returns to on/off state at power loss)
Factory default value is
2022*#
(fence returns to on/off state at power loss)
A complete power failure occurs when the unit shuts down due to the internal battery
running flat during a prolonged mains power failure.
*Can be directed to a specific zone, using KEYPAD ZONE FOCUS.
FENCE CONDITION CHECK LEVEL
2 0 1 _ * #
Sets the value at which the CHECK message will be displayed should the fence condition
indicator reduce to or below this set value.
? = check level between 4 and 7
Programmable range is
2014*#
(4 = poor) to
2017*#
(7 = fair)
Factory default value is
2014*#
(4 = poor)
*Can be directed to a specific zone, using KEYPAD ZONE FOCUS.
FENCE CONDITION ALARM LEVEL
2 7 0 _ * #
Sets the value at which the BAD message will be displayed, and at which the alarm will
sound, should the fence condition reduce to or below this set value.
? = alarm level between 0 and 4
Programmable range is
2700*#
(0 = bad) to
2704*#
(4 = poor)
Factory default value is
2701*#
(1 = bad)
The alarm level must always be set below the check level for the new setting to be
accepted.
*Can be directed to a specific zone, using KEYPAD ZONE FOCUS.
Programmable options
23
?
?
?