4. Technical Specification

120W version

300W version

Input Voltage

150-264V AC/DC or 110-254V AC/DC

Input Current (230Vac, full load)

0.52A

1.4A

Consumption

120W

300W

Power Factor (230Vac, full load)

>

0.97

Mains Frequency

50/60Hz

Inrush Current  (I

peak

 @50%)

53A, ∆t < 300µs

60A, ∆t < 300µs

Total Harmonic Distortion (230Vac, full load)

≤3%

IP Rating

IP66

Weight (std)

22Kg

23Kg

Dimensions

See previous pages for line diagrams

ATEX  and IECEx and UKEX Rating

See page 6

Twidth

Inrush Current Typical Curve

Ipeak

3. Maintenance

1.

It  is  essential  that  all  RH  units  are  maintained  in  accordance  with  the 

requirements  of  the  EN60079-17  standard:  (Electrical  apparatus  for  explosive  gas 

atmospheres – other than mines).

2.

IMPORTANT

.    No  modifications  are  permitted  to  the  unit,  all  spare  parts  must  be 

purchased  from  the  manufacturer,  unauthorized  modifications  or  spare  parts  will 

invalidate certification and make the equipment dangerous.

3.

Isolate the RH unit from the mains supply and allow to cool before carrying out any 

maintenance work.

4.

The unit has 2 independent power supplies; in the event that a power supply needs to be 

replaced remove the flameproof cover to get access to the power supply. Remove the 

power supply from the mains terminals then remove LED red and black wires. If 

replacing a power supply on a Zone 2 luminaire the orange silicone gasket should be 

replaced at the same time to maintain the restricted breathing properties of the 

enclosure,  the  gasket  is  located  in  the  machined  groove,  all  replacement  gaskets 

must be supplied via Nemalux 

5.

Disposal  of  packaging,  RH  units  and  old  LED  assemblies/power  supplies should be 

carried out in accordance with national regulations.

PROTECTION/CERTIFICATION

PROTECTION/CERTIFICATION – ZONE 1/21 VARIANTS
CML17ATEX1148 or IEC Ex CML17.0074 or CML21UKEX1102

II 2 GD Ex db eb mb IIB T4 Gb 

Ta -50

o

C to +50

o

C

Ex tb IIIC T104°C Db

Ta -50°C to +50°C

IP66 150-264V AC/DC or 110-254V AC/DC

PROTECTION/CERTIFICATION – ZONE 2/22 VARIANTS
CML17ATEX4149 or IEC Ex CML17.0074 or CML21UKEX4101

II 3 GD Ex nR ec IIC Gc   

Ta -50

o

C to +50

o

C

Ex tb IIIC T104°C Dc

Ta -50°C to +50°C

IP66 150-264V AC/DC or 110-254V AC/DC

PROTECTION/CERTIFICATION – ZONE 21 DUST ONLY VARIANTS
CML18ATEX3161 or IEC Ex CML18.0087 or CML21UKEX3107 Ex tb  

IIIC T104°C Db

Ta -50°C to +50°C

IP66 150-264V AC/DC or 110-254V AC/DC

6

-

1

2

www.nemalux.com  |   [email protected]  |   Tel 403•242•7475  |   Fax 403•243•6190 

SUBJECT TO CHANGE WITHOUT NOTICE

MADE IN 

UK

7

-

1

2

www.nemalux.com  |   [email protected]  |   Tel 403•242•7475  |   Fax 403•243•6190 

SUBJECT TO CHANGE WITHOUT NOTICE

MADE IN 

UK

Содержание RH-20 Series

Страница 1: ...ical Specification Trouble Shooting Important information The RH 20 25 series of explosion protected floodlights highbay are specialist devices certified for use in specific operating environments The...

Страница 2: ...ot exceed a temperature rise of 20 C above the ambient conditions select suitable cable 8 To ensure the safety of the equipment ensure that the flamepath on Zone 1 variants are free from any corrosion...

Страница 3: ...ed correctly and replace terminal block cover Tighten to 4Nm 10 If carrying out Insulation Resistance tests the normal method of insulation testing is to connect Live and Neutral together and test bet...

Страница 4: ...ove the power supply from the mains terminals then remove LED red and black wires If replacing a power supply on a Zone 2 luminaire the orange silicone gasket should be replaced at the same time to ma...

Страница 5: ...ned on at the source 4 If LED panel fails to light is it possible to identify if problem is with LED panel or power supply by swapping LED cables to opposite power supply to help identify problem Max...

Страница 6: ...GE WITHOUT NOTICE MADE IN UK Raytec Ltd Unit 15 Wansbeck Business Park Rotary Parkway Ashington Northumberland NE63 8QW United Kingdom RH Spartan range of High Power Floodlights CML New Port Road Elle...

Страница 7: ...2589 P 1 403 242 7475 F F 1 403 243 6190 E info nemalux com W www nemalux com Industrial LED Lighting designed to solve harsh and hazardous lighting challenges 12 12 www nemalux com sales nemalux com...

Отзывы: