Boiler Room Design 

 

 

 

 

 

The size of the chimney opening must match the amount of flue gases the chimney has to lead away.  

If the opening in the chimney is too small, this will prevent the smoke from exiting fast enough due to 

the large resistance in the chimney. This could cause the smoke to turn back; thus allowing for toxic 

fumes to enter into the house. Simultaneously, the pellet fuel may not be completely burned, due to the 

lack of oxygen for combustion. This can cause traces of soot to sit in the chimney and create what is 

called shining soot, which increases the risk of chimney fire.  

The chimney opening must also not be too large since cold air can enter the chimney from the top. 

When the chimney becomes cooled, condensation can occur and develop soot inside the chimney. 

Soot is mostly a cosmetic problem, because it can penetrate through the chimney and cause ugly 

brown splotches to appear on the walls inside the house. 

In addition, it is important that the chimney protrudes high enough above the roof so the smoke does 

not bother the surrounding houses. Environmental authorities have the possibility of prosecuting you if 

there are neighbors that complain about the smoke or odor. 

 

What signs are there, if the chimney is not working? 

Light sensor is sooty or melted. 

Smoke in the hopper. 

Warm drop shaft. 

Smoke billows out of the fan or boiler during startup.  

 

If you have any problems with your chimney, it is a good idea to keep  

a "diary“ of any draft problem; as draft problems are often associated  

with wind in certain directions. 

Wind blowing on one side of the house can cause under pressure on  

the other side of the house.  

Overpressure and under pressure will try to balance out-  

even through a chimney if possible. It is a good idea to ask your  

chimney sweeper about the size of the chimney and flues, the location of  

chimney cleaning doors, and whether it is required to have steps on the roof. 

He will also perform a fire prevention inspection. 

 

6. Air. 

The pellet boiler should be supplied with enough air for combustion. This can be achieved if the pellet 

boiler is installed in a room which is equipped with a sliding window with an adjustment bracket,  an 

adjustable air vent from the outside, or by providing the combustion chamber with air through a duct 

from the outside. The area size of the fresh air valve should generally be the same as the internal 

diameter of the chimney.  It should also be mounted on the same side as the chimney to compensate 

for any pressure differences. 

Note: 

that drum dryers, range hoods, oil burner in the same room, all use high pressure blowers, 

that steal the air in the room! 

 

7. Water tap. 

There must be a tap in the boiler room. If the boiler output is less than 60 kW,  

a powder extinguisher(at least 5 kg) will suffice. 

 

 

Содержание V7

Страница 1: ...NBE PELLETS SYSTEM V7 V10 EN303 5 2012 Class 5 approved by DTI Approved for expansion vessel Energy class AA Manufacturer NBE Production A S Brinken 6 10 ster Vr Denmark www nbe dk...

Страница 2: ...scribed here in this manual It is recommended to study the menus prior to initial start Save this manual so you always have it available when needed Page 3 Comments on the Manual Page 4 Boiler Specifi...

Страница 3: ...indication of improper draft of the chimney all operation of your system must cease immediately and must remain so until a solution to the draft problem has been resolved Continuing operation may res...

Страница 4: ...ing Efficiency 93 3 93 4 94 7 91 4 EN Class 5 5 5 5 Output 10kW 14kW 24 kW 48kW 300 ELAB 1683 1700 1765 1859 Black Star BS20 BS30 BS30 BS40 Height mm 980 980 980 1084 Width mm 430 530 530 628 Depth mm...

Страница 5: ...4kW burner Up to 110kg day 60 watt hour Weight 12kg 30kW burner Up to 150kg day 80 watt hour Weight 15kg 40 60kW burner Up to 300kg day 150 watt hour Weight 30kg 80 120kW burner Up to 600kg day 200 wa...

Страница 6: ...stance to prevent temperatures from reaching an excess of 80 C This requirement applies even if the combustible material is covered with non flammable material If the distance is greater than 500 mm t...

Страница 7: ...oke in the hopper Warm drop shaft Smoke billows out of the fan or boiler during startup If you have any problems with your chimney it is a good idea to keep a diary of any draft problem as draft probl...

Страница 8: ...xcept oil for oil burners The floor must be kept free of spilled fuel dust and combustible waste as well as waste from other activities in the room Any burning embers must be extinguished with water a...

Страница 9: ...degrees Buildings with a roof slope that is less than 20 degrees and is adjacent to another building Buildings with a slope greater than 20 degrees Buildings with a slope greater than 20 degrees and h...

Страница 10: ...mall Heat for the house is supplied while hot water is being produced 3 DHW with 3 way valve Typically used when the water heater is large and when the surface coil is large The house is not supplied...

Страница 11: ...r must not be installed on combustible surfaces 3 Un insulated smoke pipe must not exceed 0 30 m long and must be provided with an access door 4 Chimney draft should be a min 5 PA and be stable Overpr...

Страница 12: ...tor on the burner 6 Install electricity for safety cut off thermostat according to the wiring diagram SAFETY THERMOSAT MUST ALWAYS BE FUNCTION TESTED The thermostat can be tested by using an electric...

Страница 13: ...tween C and C2 is interrupted and that the high limit safety thermostat is triggered To re activate the thermostat press hard on the red button marked B in the drawing You will also hear a click signa...

Страница 14: ...l Hopper Available in 4 different models 60x60cm 200L 140 kg 80x80cm 320L 220kg 80x140cm ext 500L 350kg 100x100cm 500L 350kg Fabric hopper Available in 3 different models with gate over the auger inle...

Страница 15: ...our vacuum transport Big bag Throw the mole in the bag Easy way to transport 1 ton Flat bottom hopper Is a top fed option that maximizes space by minimizing ceiling height requirements V bottom hopper...

Страница 16: ...may be factory installed wiring on the outputs L5 L10 L5 may be factory fitted for the moving grate L6 may be factory fitted for the compressor cleaning Remove these if there is a need for other equi...

Страница 17: ...output for equipment EKSTRA 3 PE N L9 Optional output for equipment EKSTRA 3 PE N L10 Optional output for equipment BUS GRD TX RX Expansion module ILT V1 V V2 O2 controller KONTAKT K K1 External ON O...

Страница 18: ...Cleaning L Cleans the burner head efficiently with high pressure Low noise compressor included Solar Heating Use the pellet burner controller to run your solar system External Temp Sensor Stops burne...

Страница 19: ...that the controller is online If you do not have the possibility of a direct cable connection these adapters picture on right can be used They can establish a connection to your router through your h...

Страница 20: ...will now have your own page with your own burner dashboard After a short period of time you should see data streaming from the burner Do you want data on your mobile phone Then download our App for t...

Страница 21: ...your graphs You will be contacted by E mail where we ask your permission to make changes NBE will assess your graphs and the burner reaction pattern and make adjustments based on the observations You...

Страница 22: ...le flame at 10 power 6 Once the burner is activated an ignition will be made After approx 20 minutes the burner will reach a nominal output 100 If necessary lock the burner output at 100 Now you can p...

Страница 23: ...surfaces inside the boiler must be brushed clean from any deposits and the ash can must be emptied When empting the ash can pay special attention to any build up of ash in the rear smoke chamber and f...

Страница 24: ...01 04 12 Kg 87 Empty ash container 1000 ON NEJ 01 12 13 19 Cleaning of semi cleaning 2000 ON NEJ 31 12 12 25 Cleaning under burning grate 1000 ON NEJ 31 12 12 50 Cleaning of fan 5000 ON NEJ 31 12 12 0...

Страница 25: ...grate is fitted wrong Mount it correctly Too high chimney draft Install a draft stabilizer in the chimney Set electric ignition power up Reduce the fan speed during ignition Stopped fan Check if the f...

Страница 26: ...ate with pipe insulation Too many electric ignitions Flow in the system is fluctuating Set the pressure controlled circulation pump to fixed pressure External thermostat unstable Set External wait up...

Страница 27: ...ir flow in the boiler and carries more moisture 1 more oxygen costs approx 0 5 in efficiency 10 Remove the retarder Turbolator Decreases resistance of the boiler and get a bad chimney to work better T...

Страница 28: ...de by agreement with NBE To the extent that NBE is liable to the purchaser NBE s liability is limited only to direct loss and not to damages incurred by connected equipment and or indirect damage loss...

Страница 29: ...CE Declaration of Conformity...

Отзывы: