Installation of the Burner.
Temperature sensor on the boiler:
Mount the sensor within a sufficiently long
thermo well.
Use a fastening strip or similar to prevent
accidental slippage.
Safety thermostat:
Mount on either the left or right side of the boiler
as displayed in image.
Note
: Functional testing of the high limit safety
thermostat is required before starting up the boiler.
To test, press moderately on the disc (shown in A)
in the direction towards the temperature feeler. A
small "click“ will occur, signaling that the
connection between C and C2 is interrupted and
that the high limit safety thermostat is triggered. To re-activate the thermostat, press
hard on the red button marked (B) in the drawing.
You will also hear a "click", signaling that the
connection between C, and C2 is restored and
that the high limit safety thermostat is activated
and ready for use.
Semi cleaning on BS1016, BS2030 and BS4050:
The boiler cleaning system must be connected with
230V AC through the socket located on the back of
the boiler.
In the control box, make a connection to output
(L5-L10). The cleaning system will run every time
the burner conducts a blower cleaning sequence, ie.
typically 5 sec. every 10 min. These settings can be
configured under the Cleaning menu in the controller.