RELAY OPERATION

 

Relays can be programmed via 

SETTINGS/Relays

, each relay can be connected to any of the four tanks (multiple relays can be 

connected to same tank), and can preform various outputs depending on parameters.

 

 

Current relay status is indicated by four relay status lights located on front panel, light is turned on when relay is closed. 
Upper most relay status light indicates state of relay 1, second relay 2, third relay 3 and bottom most represents relay 4.

 

 
Each relay can operate in 5 different modes:

 

 

Off

 

– Relay is constantly switched off

 

HI 

 

This mode operates with “Alarm level” parameter. Relay will become active, once measured level is greater or equal to “Alarm 

level” parameter, once measured level falls below “Alarm level”, relay will deactivate.

 

LO 

 

This mode is opposite of HI mode, relay will become active, once measured level is less or equal to “Alarm level”, once measured 

level is greater than “Alarm level” relay will deactivate. 

 
Pump in 

 

In this mode additional parameters “Pump HI level” and  

“Pump LO level” must be set. 
Relay will become active once measured level is less or equal to 
“Pump LO level” and will remain active until measured level is equal or 
greater than “Pump HI level”, at which relay will deactivate. 
When relay is operating in this mode “Alarm” setting is not used 
and relay operation will not trigger light or sound alarm.

 

  

 

 

 

 

 

 

 

 

 

 

 

Figure 7. Pump in relay mode

 

 

Pump out 

In this mode additional parameters “Pump HI level” and  

“Pump LO level” must be set. 
Relay will become active once measured level is greater or equal to 
“Pump HI level” and will remain active until measured level is less or equal 
to “Pump LO level”, at which relay will deactivate. 
When relay is operating in this mode “Alarm” setting is not used 
and relay operation will not trigger light or sound alarm. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 8. Pump out relay mode

 

 
Relay outp

ut can be inverted by selecting N/C (Normally Closed) relay “Type”. 

Relay modes “HI” and “LO” support “Alarm” option, if this parameter is set to “On”, relay activation will cause light and sound alarm to 
be triggered.

 

Warning: Use relay outputs according to relay specifications to prevent device damage!

 

 
ALARMS

 

Alarms are signalized via buzzer for sound signal and two lights on top of the front panel of the receiver. 
 
Red (left) alarm light and sound signal will activate when user set alarm 

condition is met, conditions can be programmed in “Relays” 

sub-

menu, refer to chapter “SETTINGS/Relays”. This alarm can be disabled by setting parameter “SETTINGS/Relays/Alarm” to off. 

Please note setting “SETTINGS/Relays/Mode/Pump in(out)” do not support alarms. 
 
Yellow (left) alarm light and sound signal will activate when any of the “internal alarms” are triggered. These alarms can not be 
disabled.

 

 

INTERNAL ALARMS

 

 

Measurement error: when measurement error occurs - measurements are out of bounds. 

 

Sensor error: sensor has detected error during measurement, please refer to sensor manual for troubleshooting. 

 

ENABLING/DISABLING ALARM

 

Sound alarm can be muted/un-muted by holding UP button for more than 2 seconds while not in settings menu, crossed bell icon will 
appear on all main screens while alarms are muted. Sound alarm is also un-muted when device is restarted.

 

 
Alarm function can be disabled altogether for each relay, f

or relay alarm settings refer to chapter “RELAY OPERATION”.

 

Internal alarms light can 

not

 be disabled, however sound can still be muted. 

 

4-20 MA OUTPUT (LW410XW/D AND LW410XL/D MODELS)

 

Outputs are connected to tank 1 and tank 2 as marked on relay board label. 
20 mA is driven by level percentage linearly between 4 mA (empty tank 

– 0 %) and 20 mA (full tank – 100 %). 

If tank is in error state 3.6 mA is outputted. 
 
Please note that voltage output is equal to receiver supply voltage.

 

 

Содержание LW410

Страница 1: ...play unit can be mounted onto the ferrous surface with four mounting magnets optional accessories or with mounting screws not included to any flat surface Mounting the display unit with screws Unscrew...

Страница 2: ...muted SD icon is shown if SD card is inserted and working properly only on LW410XL D model WiFi icon is shown when WiFi connection is established blinks when display unit transmits data to LiveData po...

Страница 3: ...1 year history each column represents 15 days column is written on 1st and 15th of a month...

Страница 4: ...cating that the display unit doesn t receive data from the sensor sensor is off or out of range SETTING MINIMAL AND MAXIMAL LEVELS To ensure proper measurement please set minimal and maximal level val...

Страница 5: ...ion will not trigger light or sound alarm Figure 8 Pump out relay mode Relay output can be inverted by selecting N C Normally Closed relay Type Relay modes HI and LO support Alarm option if this param...

Страница 6: ...ssing It is recommended to preform monthly backup of data to personal computer or any other memory storage device When using a new SD card it is recommended to format it in FAT32 and preform a test wr...

Страница 7: ...Reattach the front panel of the display unit and tighten four plastic screws do not use excessive force to tighten plastic screws...

Страница 8: ...screen Settings General Default Range Description Reset history No No Yes Reset history charts of the device Language English English Slovene Language of device interface Time and date Time 12 00 Time...

Страница 9: ...on audio visual alarm when relay is ON Off This relay is not connected to audio visual alarm Back Return to main settings menu Settings WiFi Default Range Description Scan for WiFi Scans for available...

Страница 10: ...range to AP No internet AP does not have connection to world wide web internet Check if device has sensor connected and is receiving data Interrupting and weak sensor signal check for obstructions be...

Страница 11: ...d insertion or settings change File types csv comma separated values Real time clock battery preinstalled 1 x 3 V CR2032 Lithium Models LW410 D receiver level display LW410XW D receiver level display...

Отзывы: