NFC Service Manual 63
Version 1.0
4.12.12 Dual Venturi
Part
Check Point
Function
Controls the amount of mixed gas to modulate heating input.
It uses synchronous motor to control the amount of mixed gas by stage 1 and 2.
Failure Event
1. Blade not closing
2. Blade not opening
3. Gas plunger does not disengage.
Effects
1. Frequent On / Off due to excessive heat
2. Fail to reach the set temperature due to lack of heat
3. Loss of flame during higher modulation stage 2 operation
Error Code
E012, E060
Diagnostic
1. Voltage check : Checking the voltage of synchronous motor
(Approximately after 2 sec of Open / Close operation, the motor turns off.)
2. Checking operation in MIN2
Содержание NFC-175
Страница 133: ...Memo...
Страница 134: ...Memo...
Страница 135: ...Memo...
Страница 136: ...Memo...
Страница 137: ...Memo...