The following table lists the product information requirements (EU regulation No 811/2013 and No 813/2013)
KD Navien
Symbol
Unit
NCB-20LHWE NCB-23LHWE NCB-28LHWE NCB-33LHWE
Condensing boiler
YES
YES
YES
YES
Low-temperature (**) boiler
NO
NO
NO
NO
B1 boiler
NO
NO
NO
NO
Cogeneration space heater
NO
NO
NO
NO
Combination heater
NO
NO
NO
NO
Rated heat output
P
rated
kW
20
23
28
33
Seasonal space heating energy
η
s
%
92
93
93
93
Useful heat output
At rated heat output
and high-temperature regime (*)
P
4
kW
19.5
23.4
28.3
33.2
At 30 % of rated heat output
and low-temperature regime (**)
P
1
kW
6.5
7.8
9.4
11.1
At rated heat output
and high-temperature regime (*)
η
4
%
87.8
87.9
87.9
87.8
At 30 % of rated heat output
and low-temperature regime (**)
η
1
%
97.8
98.1
97.7
98.0
Auxiliary electricity consumption
At full load
elmax
kW
0.036
0.045
0.048
0.045
At part load
elmin
kW
0.014
0.015
0.016
0.016
In standby mode
P
SB
kW
0.003
0.003
0.003
0.003
Other items
Standby heat loss
P
stby
kW
0.080
0.080
0.084
0.084
Ignition burner power
consumption
P
ign
kW
-
-
-
-
Annual energy consumption
Q
HE
GJ
37
43
52
57
Sound power level, indoors
L
WA
dB
50
52
54
52
Emissions of nitrogen oxides
NO
x
mg/kWh
36
38
30
37
Contact details
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).
Read the user’s information and installation manual before the application is assembled, installed or maintained.
3000 Cathedral Hill, Guildford, Surrey, GU2 7YB
10 About the Boiler
Содержание NCB-20LHWE
Страница 41: ...41 Wiring Examples for Different Applications...
Страница 71: ...71 13 4 Ladder Diagram 3 15A Appendices...
Страница 75: ...Memo...
Страница 76: ...Memo...
Страница 77: ...Memo...
Страница 78: ...Memo...
Страница 79: ......