Nature Power 38330 Скачать руководство пользователя страница 11

 

   

Page 

11 

   

   

   

Green  

LED 

ON 

(flashing) 

Pass-Through Mode (AC mode). Battery Charging is in progress. 

Remote LCD Display shows:  

  -  Battery DC Voltage and charging current  

  -  AC Input Voltage and Current 

     e.g.   

AC:  120V       20A        DC:  12.0V      50A 

Press ‘+’ or ‘-‘ key to check charging stage. 

     e.g

.     Charge Stage ABS 

Press ‘+’ or ‘-‘ key to check AC Input Power. 

     e.g

.      System Power           2.4 KW 

Fault 

Red  

LED ON 

(solid) 

Unit has shutdown. Display shows error code and error message.  

-  Low battery shutdown 

 e.g.  

FAULT:    E01              Low Battery 

 

 

 

Push Button Functions on Unit 

  A beeping sound will occur every time that any button on the unit is triggered.  

 

Button 

Function 

Power 

Turns unit On/Off. Press and hold for 1 second to turn unit On/Off 

Reset 

Reset the unit: Press once to reset the unit. This may be required when an error 

is detected on the unit 

 

Push Button Functions on Remote Display 

 A beeping sound will occur every time any button on the unit is triggered. 

 

Button 

Function 

Turns LCD display On/Off. Press and hold for 2 seconds to turn display On/Off. 

Display shows unit model number and revision. 

   e.g.      

Nature     38330  

               Power     

 

REV 1.1

 

Enter 

Save the selected setting or go to the next stage 

Scroll up on the menu 

Scroll down on the menu 

EXIT 

Exiting or entering the feature setting mode 

 

Understanding the Charger Functions 

Three-Stage Charging: 

The Three-Stage Charging algorithm has a Bulk, then Absorption and then Float sequence. 

During the Bulk stage, the battery accepts the maximum constant current from the charger. In 

the Absorption stage, the battery voltage is held to constant voltage and the charging will 

slowly reduce. In Float stage, the charger continuously produces voltage at a lower level to 

fully top up the battery and maintain the battery in a fully charged state. 

The charger will automatically restart the charging cycle in Bulk stage if the battery is 

discharged to 12.5V. Also, after seven days, the charger will automatically restart the 

recharging cycle to refresh the battery. 

 

Battery Type: 

Three types of battery setting (GEL, AGM and Flooded) are available. See reference battery 

charging voltage as shown: 

 

Battery Type 

Absorption 

Float 

Equalization 

GEL 

14.4 V 

13.8 V 

N.A. 

AGM 

14.3 V 

13.45 V 

N.A. 

Flooded 

14.4 V 

13.5 V 

16.0 V 

 

Equalize the Flooded Battery: 

For Flooded battery type, equalization mode is available. Use the following procedure to 

equalize the flooded battery. See also section 5 on setting EQ mode for flooded battery. 

DANGER: 

Explosion Hazard. The flooded battery generates explosive gases 

during equalization. Follow all the battery safety precautions listed in the manual.  

CAUTION:

 Risk of Battery and Equipment damage. Only a Flooded lead-acid battery can 

Содержание 38330

Страница 1: ...3000W Pure Sine Inverter Charger 38330 Owner s Manual SINGLE COLOR Used for background colors other than Black or White White Used for black or dark grey background color ...

Страница 2: ...de Nature Power assumes no responsibility for errors or omissions Note as well that specifications and product functionality may change without notice Important Please be sure to read and save the entire manual before using your Nature Power Inverter Misuse may result in damage to the unit and or cause harm or serious injury Read manual in its entirety before using the unit and save manual for fut...

Страница 3: ...way from children Avoid moisture Never expose unit to snow water etc Unit provides 120 VAC treat the AC output the same as regular wall AC sockets at home DANGER Explosion hazard DO NOT use the unit in the vicinity of flammable fumes or gases such as propane tanks or large engines AVOID covering the ventilation openings Always operate unit in an open area Prolonged contact to high heat or freezing...

Страница 4: ... Page 4 Table of Contents 1 INTRODUCTION 5 2 PRODUCT DESCRIPTION 5 3 INSTALLATION 6 4 UNIT OPERATION 10 5 TROUBLESHOOTING 13 6 SPECIFICATIONS 15 7 WARRANTY 16 ...

Страница 5: ...multi stage charging capability to minimize charging time The Power Factor Corrected PFC input minimizes AC input current required for charging Optional Battery Temperature Sensor BTS is available and used to sense the battery temperature to correct charging voltage to ensure the battery is fully charged A Manual Equalization Mode is built in to improve the life and performance of flooded batterie...

Страница 6: ... line The voltage between each line to neutral is 120Vac Input AC Source from Dual Input The dual input has 2 line inputs 1 neutral and 1 ground The two 120Vac lines are in phase and must come from the same source AC Loads In Battery Inverter mode the unit s AC Output L1 and L2 lines are connected together to provide 120Vac on both lines In Pass Through mode the AC source connected to the unit s A...

Страница 7: ...gh the ground stud of the unit DC Fuse or Over Current Protective Device A DC rated fuse or a DC rated over current protective device connected along the DC positive line is required Based on the National Electrical Code requirement a fuse or circuit breaker with a minimum of 350 Adc is required Based on the size of your 12V Battery Bank determine the overall short circuit current rating of the ba...

Страница 8: ...n a separate well ventilated compartment Do not install the unit in any compartment containing flammable gases or liquids like gasoline or in the battery compartment where they may be explosive hydrogen gas from the batteries present The length and size of the DC cables will affect unit performance For indoor use the unit can be mounted in any direction except with the fan panel panel with fan ope...

Страница 9: ... to the battery negative terminal Make sure the DC Disconnect Switch is in the OFF position Connect one end of the positive DC input cable to the Inverter Charger DC positive terminal Connect the other end of the positive DC input cable to one of the terminals of the DC Disconnect Switch Connect a DC input cable between the other terminal of the DC Disconnect Switch and one side of the terminal of...

Страница 10: ...s Non Backup Mode Same as Auto Backup Mode but when there is a power failure of the utility or the AC input source is not available the inverter will not turn ON automatically You are required to manually turn ON the inverter This setting is the same as factory default but with Inverter set to OFF Understanding the Display Functions LED Indicator functions on unit display and remote display Status...

Страница 11: ...ting mode Understanding the Charger Functions Three Stage Charging The Three Stage Charging algorithm has a Bulk then Absorption and then Float sequence During the Bulk stage the battery accepts the maximum constant current from the charger In the Absorption stage the battery voltage is held to constant voltage and the charging will slowly reduce In Float stage the charger continuously produces vo...

Страница 12: ...arging Voltage Adjustment from 25 C normal setting Flooded and GEL type AGM type 25 C 0 027 V C 0 021 V C 25 C 0 V 0 V 25 C 0 027 V C 0 021 V C Note The charger will terminate battery charging when the BTS senses the battery temperature reaching 60 C It will not continuously make voltage adjustments when the battery temperature drops to below 0 C Understanding the Error Codes Error Code on Display...

Страница 13: ...er On Off Turns Power Inverter On Off SCR set 15 20 25 30 A Set AC Input Source Power Breaker Rating During by pass mode with high demand for AC power for the load the charger current is reduced automatically to prevent the tripping of the AC Source power breaker Power Save 0 5 10 15 20 50W Lowers power draw when low power loads are connected to inverter Battery Type AGM GEL Flooded Select battery...

Страница 14: ...n be restarted No AC output Fault LED is on 30A Circuit Breaker is tripped and check fault code Check load and reset the AC breaker and verify the error condition and make correction Condition Inverter setting is set to On AC source is not available No AC Output Battery Power LED is off Unit is turned Off Turn unit ON by following the instruction as in Section 4 No DC power to unit Battery voltage...

Страница 15: ...t L1 N1 30A AC Output Line 1 L1 N1 and Line 2 L2 N2 30A Remote Display Display Panel Port RJ45 socket LCD Display AC Input Output Voltage Current DC Input Output Voltage Current Battery Temperature Sensor Port BTS Port RJ45 socket Charger Charging Voltage Range 7 16 VDC Floated Voltage Range 13 45 13 8 VDC Charging Control 3 Stages Bulk Absorption Float Charger Current max 150A Charger Current Set...

Страница 16: ...o retail store After speaking to a customer service representative if products are deemed non working or malfunctioning the product may be returned to the purchasing store within 30 days of original purchase Any defective unit that is returned to manufacturer within 30 days of the date of purchase will be replaced free of charge If such a unit is returned more than 30 days but less than one year f...

Отзывы: