Preparing for Installation 

Typical Wiring block diagram of the Power Inverter: 
 
 
 
 
 
 
 
 
 
 

12V Battery Bank: 

  The use of deep cycle battery is highly recommended for power inverter application 

  For battery size, you need to identify what you wish to operate, and for how long. NATURE 

POWER recommends that you purchase as much battery capacity as possible. See more on 
Battery Run time and Load in Section 4. 

 
Fuse or Circuit Breaker:   

  DC-rated fuse or DC-rated circuit breaker connected along the DC positive line is required. 

  For 32326, select a fuse or circuit breaker with a minimum of 300 Adc 

  Based on the size of your 12V Battery Bank, determine the overall short circuit current rating of 

the battery bank from the battery manufacturer. The fuse or circuit breaker chosen has to be 
able to withstand the short circuit current that may be generated by the battery bank 

 
Disconnect Switch: 

  Select a DC Disconnect Switch with the same or higher rating of the selected fuse or circuit 

breaker. 

  The DC Disconnect Switch is used to disconnect the DC power between the unit and the battery 

bank during service, maintenance or trouble shooting. 

 
DC Input and Grounding Cable: 

  Use of low resistance wire is required for all the DC connections between the unit and the 

battery bank. 

  For 32326, use minimum #2/0 AWG wire with maximum cable length of 5 feet. 

Important: 

The unit is grounded through the ground stud of the unit located near the DC Input 

terminal. 

  For the grounding cable connected between the unit

’s chassis and the earth ground, use a 

matching cable size as used on the DC Input Cable section.  

 
 

AC Input Source and Branch Breaker: 

  Standard AC Input wire is required for all the AC connections between the AC source & the AC 

Input port, and the AC Output ports to load.  

  A 30A branch circuit breaker is required to connect between AC Input source and unit

’s AC Input 

port.  

Important: 

Follow the electrical and or building code when you connect the unit to any AC source. 

  

Installing the Inverter-Charger System 
WARNING

Electrical Shock Hazard

 

The unit ‘On/Off’ switch does not disconnect the DC power from the battery. Use the DC 
Disconnect Switch or disconnect the DC input cables connection to disconnect the DC 
power from the battery before working on any circuits connected to the unit. Failure to 
follow these instructions can result in death or serious injury. 
 

 
 
 

Inverter-Charger 

 

(32326) 

DC Disconnect 

Switch 

Fuse or Circuit 

Breaker 

 
 

12 V Battery Bank 

 
 

Output: 

AC Output 

Port 1-3 & 

USB  

Branch 

Breaker 

Input: 

AC Source 

Содержание 38326

Страница 1: ...Version 1 1 1 Inverter 2000W with 55Amp Inverter Charger 38326 Owner s Manual ...

Страница 2: ...een taken to ensure the accuracy of the contents of this guide Nature Power assumes no responsibility for errors or omissions Note as well that specifications and product functionality may change without notice Important Please be sure to read and save the entire manual before using your Nature Power Inverter Charger Misuse may result in damage to the unit and or cause harm or serious injury Read ...

Страница 3: ...Page 3 Table of Contents 1 INTRODUCTION 4 2 PRODUCT DESCRIPTION 5 3 INSTALLATION 5 4 UNIT OPERATION 9 5 TROUBLESHOOTING 11 6 SPECIFICATIONS 14 7 WARRANTY 15 ...

Страница 4: ...occurs cleanse right away with soap and water for a minimum of 15 minutes and seek medical attention Batteries produce explosive gases DO NOT smoke or have an open spark or fire near the system Keep unit away from moist or damp areas Avoid dropping any metal tool or object on the battery Doing so could create a spark or short circuit which goes through the battery or another electrical tool that m...

Страница 5: ...al safety wiring regulations and installation codes Failure to follow these instructions can damage the unit and could also result in personal injury or loss of life CAUTION Before beginning unit installation please consider the following The unit should be used or stored in an indoor area away from direct sunlight heat moisture or conductive contaminants When placing the unit allow a minimum of t...

Страница 6: ...nding Cable Use of low resistance wire is required for all the DC connections between the unit and the battery bank For 32326 use minimum 2 0 AWG wire with maximum cable length of 5 feet Important The unit is grounded through the ground stud of the unit located near the DC Input terminal For the grounding cable connected between the unit s chassis and the earth ground use a matching cable size as ...

Страница 7: ...the OFF position Connect one end of the positive DC input cable to the Power Inverter DC positive terminal Connect the other end of the positive DC input cable to one of the terminals of the Disconnect Switch Connect a DC input cable between the other terminal of the Disconnect Switch and one side of the terminal of the fuse holder Connect a DC input cable between the other terminal of the fuse ho...

Страница 8: ...is limited to 16 6A for 2000W model 32326 Remote Display Connection The Remote Display on the unit is detachable To install the remote to different location an optional 6 pin standard RJ12 cable not provided is required Remove the 2 screws at the front of the Display Panel and remove the small RJ12 cable Install the optional RJ12 standard cable to your desired location Please note polarity Connect...

Страница 9: ... Display LED Display Function Status Green solid Green Ful By Pass Mode Battery is fully charged Green flashing OFF bul By Pass Mode Battery charging in progress and is in BULK mode OFF abs By Pass Mode Battery charging in progress and is in ABSORPTION mode Amber solid Green 12 5 Battery Mode inverter is running display shows battery voltage in DC volts Amber 0 80 Battery Mode inverter is running ...

Страница 10: ... high Check battery setting E11 Battery bad Battery did not accept charge E12 Internal transfer switch temperature is high and shutdown occurs Reduce load and check if any ventilation of the unit is blocked AC Load on Inverter Although the Power Inverter can provide high surge power up to two times the rated output power some high surge loads like sump pumps heavy duty motors etc may still trigger...

Страница 11: ...5A 4A 55A 6A Battery Type and Voltage Setting Bulk Absorption Float FLo Flooded 14 4V 14 4V 13 5V GEL GEL 14 2V 14 2V 13 8V AG AGM 14 3V 14 3V 13 4V Fi Fixed 13 5 Vdc fixed voltage Battery Under Voltage Setting SdL Battery under voltage setting is set to LOW setting used for normal operation Under voltage alarm 11 0 Vdc Under voltage alarm recovery 11 3 Vdc Under voltage shutdown 10 5 Vdc Under vo...

Страница 12: ...ger current reduced to 5A 85 C 185 F Charger current recover back to set value Environment Temperature 60 C 140 F Charger current reduced to 5A 55 C 131 F Charger current recover back to set value Enter Function Menu for unit setting To enter unit Function Menu press and hold Power and Select button together for about 5 seconds until a beep is sounded When you are in Function Menu Press Power butt...

Страница 13: ...Page 13 ...

Страница 14: ...ns are subject to change without notices Specification 38326 Inverter AC Output Power 2000W AC Output Current 16 6A AC Surge Power Peak 4000W AC Output Voltage Frequency 120 VAC 60 Hz AC Output Waveform Sinewave 3 THD Nominal DC Input Voltage 12 5 VDC No Load battery draw 1 5 ADC DC Input Voltage operating range 10 5 15 5 VDC Under Voltage Alarm 11 0 12 1 VDC Under Voltage Alarm Recovery 11 3 12 3...

Страница 15: ... not apply to damage to units from misuse or incorrect installation connection Misuse includes wiring or connecting to improper polarity power sources If you are experiencing any problems with your unit please contact our customer service department at info naturepowerproducts com or Phone 1 800 588 0590 before returning product to retail store After speaking to a customer service representative i...

Отзывы: