5. FEATURE SETTING
To understand more about the unit features, read the following section and follow the instructions
to make changes to the desired setting.
Default Factory Setting:
In (Inverter): In1- inverter enabled in standby mode with load sense off
Cu (Charger): 55A
– charger enabled (55A for 32326)
AL (Alarm): AL1
– alarm enabled
Sd (UV shutdown): SdL
– Under voltage shutdown set to low setting
bAt (Battery type): FLo
– Flooded typed
Cb (Maximum current):
Cb3
– Maximum Shore Power Current draw is 30A
Understanding the Unit Settings
Inverter Setting
In0
Inverter is disabled, unit will not provide backup function when utility power is not
available
In1
Inverter is set to standby mode with power save mode OFF. Unit will provide
backup function when utility power is not available
In2
Inverter is set to standby mode with power save mode ON. Unit will provide
backup function only when utility power is not available AND the load connected
to the output is >10W.
Note: Unit will turns ON every 10 s to check on the power consumption.
Charger Current Setting
5A
– 40A
5A
– 55A
Bulk/Float current setting:
32326: 5A/1.5A, 15A/3A, 35A/4A, 55A/6A
Battery Type and Voltage Setting (Bulk/Absorption/Float)
FLo
Flooded: 14.4V / 14.4V / 13.5V
GEL
GEL: 14.2V / 14.2V / 13.8V
AG
AGM: 14.3V / 14.3V / 13.4V
Fi
Fixed: 13.5 Vdc fixed voltage
Battery Under Voltage Setting
SdL
Battery under voltage setting is set to LOW (setting used for normal operation)
Under voltage alarm: 11.0 Vdc
Under voltage alarm recovery: 11.3 Vdc
Under voltage shutdown: 10.5 Vdc
Under voltage recovery: 12.0 Vdc
SdH
Battery under voltage setting is set to HIGH (setting to avoid battery over
discharge when connected to car start battery)
Under voltage alarm: 12.1 Vdc
Under voltage alarm recovery: 12.3 Vdc
Under voltage shutdown: 11.8 Vdc
Under voltage recovery: 12.6 Vdc
Alarm Setting
AL0
Fault and warning audible alarm is disabled. Display panel only shows error code
and audible alarm will not sound.
AL1
Audible alarm will sound when fault or warning occurs.
Maximum Shore Power Current Draw Setting
32326
AC Load Current
Charger Current
Cb1
Set the maximum current draw from shore power to 15A. The maximum current
draw from unit is set to match with the shore power circuit breaker rating to avoid
tripping of the shore power circuit breaker during the by-pass mode. Battery
charging current will automatically reduce when there is a high demand on AC
load during the by-pass mode.
>11Aac
5 Adc