Problem: Water Dispenses from Cold or Sparkling Valve, but Water not Cold
Troubleshooting Chart
NCC7222-07 R2- 111207
11
Cause
Action
1. ION has been in SleepMode (with compressor off) for
weekend or long holiday.
1. Allow ice to build over 3-4 hour time period. Optionally,
program SleepMode to be OFF (Ice Bank to be maintained
24 hours per day).
2. ION is constantly in SleepMode
- is cooler in room with low level lighting?
- is Blue LED ON or OFF?
2. If Blue LED is OFF, this indicates ION is in SleepMode.
To lockout ION from SleepMode, see programming section in
Owners Manual.
3. ION may be plugged into outlet controlled by light switch.
3. Change Outlet and retest.
4. Is Fan operating?
4. Check wiring at Control Board.
5. Is Compressor Running?
5. Check wiring at Control Board
6. Freon Leak.
6. If no ice after 3 hours of Compressor and Fan operating,
call factory.
7. Software bug
7. Software Rev Level J and K have higher than normal incidence
of compressor malfunction – either freeze-up or no ice condition.
Call factory for replacement of product or new Circuit Board.
Содержание ION pure refreshment
Страница 1: ...NCC7222 07 R2 111207 TECHNICAL SERVICE MANUAL...
Страница 22: ...Frame Assembly NCC7222 07 R2 111207 21...
Страница 23: ...Display Valve Assembly Models 903 904 only NCC7222 07 R2 111207 22 for Models 903 904 only...
Страница 24: ...NCC7222 07 R2 111207 Filter Manifold Assembly 23...
Страница 25: ...Front Panel Assembly NCC7222 07 R2 111207 24...
Страница 26: ...Dispensing Assembly 901 NCC7222 07 R2 111207 25...
Страница 27: ...Dispensing Assembly 902 NCC7222 07 R2 111207 26...
Страница 28: ...Dispensing Assembly 903 NCC7222 07 R2 111207 27...
Страница 29: ...Dispensing Assembly 904 NCC7222 07 R2 111207 28...
Страница 30: ...Ice Bank Assembly NCC7222 07 R2 111207 29...
Страница 31: ...Final Assembly NCC7222 07 R2 111207 30...