NI 9207 Scan List
The scan list is a simple list of channels to convert, in order. The NI 9207 has 16 total channels
that can be measured.
NI 9207 Calibration Data
Calibration data is set up by driver during initialization, and the calibration conversion is
performed on the module ADC itself. Thus, you do not need to use the calibration tables.
NI 920
8
The vendor configuration extensions for the NI 9208 are listed in Table 21.
Table 19.
NI 9207 Conversion Speed Control
Speed Control
Meaning
Conversion Rate
0
High-Accuracy
62.5 ms/channel (1 s total)
1
High-Speed
1.92 ms/channel (30.72 ms total)
Table 20.
NI 9207 Scan List Format
Index
Sub
Type
Value
0x2001
0
ARR:U32
17
1
16
2
0
3
1
...
...
17
15
Table 21.
NI 920
8
Vendor Configuration Extensions
Index
Sub
Type
R/W
Description
0x2100
0
ARR:U32
—
Scan List = 17
1
R
Channels to Convert = <1..16>,
default = 16
2..17
R/W
Channel Code
0x2002
0
U32
R/W
Conversion Speed Control = 0 or 1,
default = 0