background image

Table 1.

 Hazardous Location Retention Accessories (Continued)

Port

Required Accessory

Part Number

 

 

 

Mini DisplayPort

Mini DisplayPort Cable Retention Bracket

156866-01

SD Card Slot

SD Door Kit

783660-01

Special Conditions for Hazardous Locations Use in Europe and
Internationally

The cDAQ-9132 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO
Certificate No. 12 ATEX 1202658X and is IECEx UL 14.0089X certified. Each device is
marked   II 3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures
of -20 °C ≤ Ta ≤ -55 °C.

Caution

 

You must make sure that transient disturbances do not exceed 140% of

the rated voltage.

Caution

 

The system shall only be used in an area of not more than Pollution

Degree 2, as defined in IEC 60664-1.

Caution

 

The system shall be mounted in an ATEX/IECEx-certified enclosure with

a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15.

Caution

 

The enclosure must have a door or cover accessible only by the use of a

tool.

Power Requirements

Caution

 

The protection provided by the NI cDAQ-9132 can be impaired if it is

used in a manner not described in the user documentation.

Note

 

Some C Series modules have additional power requirements. For more

information about C Series module power requirements, refer to the
C Series module(s) documentation.

Note

 

Sleep mode for C Series modules is not supported in the NI cDAQ-9132.

Voltage input range

9 to 30 V (measured at the NI cDAQ-9132
power connector)

Maximum power consumption

1

40 W

Recommended power supply

100 W, 24 VDC

1

Includes maximum 1 W module load per slot across rated temperature and product variations.

NI cDAQ-9132 Safety, Environmental, and Regulatory Information

  | 

© National Instruments

  | 

3

Содержание cDAQ-9132

Страница 1: ...ification standards than the NI cDAQ 9132 the combined system may be limited by individual component restrictions Refer to the NI cDAQ 9132 Specifications for more details Hot Surface This icon denote...

Страница 2: ...ess power has been switched off or the area is known to be nonhazardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of...

Страница 3: ...e system shall be mounted in an ATEX IECEx certified enclosure with a minimum ingress protection rating of at least IP54 as defined in IEC EN 60079 15 Caution The enclosure must have a door or cover a...

Страница 4: ...ut V1 and a secondary power input V2 The POWER LED on the front panel identifies the power input in use When the LED is lit green V1 is in use when the LED is lit yellow V2 is in use Caution Do not co...

Страница 5: ...current If the power source is connected to the power connector using long wiring with high DC resistance the voltage at the power connector may be significantly lower than the specified voltage of th...

Страница 6: ...in the product documentation Furthermore any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory...

Страница 7: ...B Host Ports Install a noise suppression ferrite National Instruments part number 711849 01 included in the shipping kit around all external USB cables attached to the USB host ports to ensure that yo...

Страница 8: ...to the NI Trademarks and Logo Guidelines at ni com trademarks for information on NI trademarks Other product and company names mentioned herein are trademarks or trade names of their respective compa...

Отзывы: