Appendix E
SCXI-1162 Cabling
© National Instruments Corporation
E-11
SCXI-1162 User Manual
SCXI-1348 Installation
Follow these steps to install the SCXI-1348:
1. Make sure that the computer and the SCXI chassis are turned off.
2. Install the SCXI module to which the SCXI-1348 will connect.
3. Connect one end of the ribbon cable to the adapter board rear connector.
4. Plug the adapter board front connector onto the module rear signal connector. A corner of
the adapter board will enter the upper board guide of the chassis.
5. Screw the rear panel to the threaded strips in the rear of the chassis.
6. Connect the loose end of the ribbon cable to the DIO-32F I/O connector.
Check the installation.
SCXI-1180 Feedthrough Panel
The SCXI-1180 feedthrough panel provides front panel access to the signals of any data
acquisition board that uses a 50-pin I/O connector. The SCXI-1180 consists of a front panel with
a 50-pin male front panel connector that occupies one slot in the SCXI chassis, and a ribbon
cable with a female rear connector and a male breakout connector. You can attach the rear
connector to the male breakout connector of an SCXI-1340, SCXI-1341, SCXI-1342,
SCXI-1344, or SCXI-1351 in the adjacent slot. The breakout connector further extends the
cabling scheme. The front panel connector has the feedthrough connection. You can attach an
SCXI-1302 terminal block to the front panel connector for simple screw terminal connections. A
rear filler panel that shields and protects the interior of the SCXI chassis is also included.
SCXI-1180 Installation
Install the SCXI-1180 to the right of a slot that has an SCXI-1340, SCXI-1341, SCXI-1342, or
SCXI-1344 cable assembly or an SCXI-1351 slot extender in its rear connector space.
Follow these steps to install the SCXI-1180:
1. Make sure that the computer and the SCXI chassis are turned off.
2. Remove the front filler panel of the slot where you want to insert the SCXI-1180.
3. Thread the rear connector through the front of the chassis to the rear of the chassis. Attach
the rear connector to the breakout connector of the adjacent cable assembly or slot extender,
as shown in Figure E-3.
4. Screw in the rear panel to the threaded strip in the rear of the chassis.
5. Screw the front panel into the front threaded strip, as shown in Figure E-4.
Check the installation.