PAGE: 38
Note: These overall dimensions are approximate /– 1".
Heat Transfer Products reserves the right to change or discontinue models without notice.
NOTE:
A BRONZE CIRCULATOR BETWEEN THE DOMESTIC HOT WATER OUTLET AND DOMESTIC COLD WATER INLET IS
REQUIRED TO ACHIEVE RATINGS BELOW:
VOYAGER SSVH MODEL SIZING CHART
Flow
TEMPERATURE RISE (DEGREES F.)
GPM
15
20
25
30
2
15,000
20,000
25,000
30,000
3
22,500
30,000
37,500
45,000
4
30,000
40,000
50,000
60,000
5
37,500
50,000
62,500
75,000
6
45,000
60,000
75,000
90,000*
7
52,500
70,000
87,500*
105,000*
8
60,000
80,000
100,000*
N/R
9
71,400**
95,200**
119,000**
124,500**
10
85,000**
113,250**
140,000**
140,000**
* FOR SSVH-130 MODELS ONLY!
**FOR SSVH-199-80 MODELS ONLY!
NOTE:
THE SUPER-E MUST BE SET 25 DEGREES F. ABOVE THE SYSTEM TEMPERATURE. THE ABOVE CHART IS BASED ON
USING THE CIRCULATOR BETWEEN THE DOMESTIC COLD WATER INLET AND THE DOMESTIC HOT WATER OUTLET. FOR
SET POINT TEMPERATURES ABOVE 120 DEGREES F., YOU MUST USE AN ANTI-SCALD TEMPERING VALVE ON THE OUT-
LET TO DOMESTIC HOT WATER FIXTURES.
VOYAGER FIRST DRAW CAPACITY (In minutes) AT 140 DEGREES F.
Model
2 GPM
3 GPM
4 GPM
5 GPM
6 GPM
7 GPM
8 GPM
SSVH90-45
20
15
9
7
5
4
3
SSVH130-45
20
16
12
10
9
7
6
SSVH199-80
00
00
15
14
13
12
10
VOYAGER FIRST DRAW CAPACITY (In minutes) AT 115 DEGREES F.
Model
2 GPM
3 GPM
4 GPM
5 GPM
6 GPM
7 GPM
8 GPM
SSVH90-45
30
23
14
10
8
6
5
SSVH130-45
31
24
18
16
14
11
10
SSVH199-80
00
00
23
21
20
18
15
MODEL
HEIGHT
WIDTH
DEPTH
INPUT
FIRST HR. RATING
SSVH90-45
42"
24"
32"
90,000
125 U.S. gallons
SSVH130-45
42"
24"
32"
130,000
180 U.S. gallons
SSVH199-80
72"
24"
32"
199,000
300 U.S. gallons
MODEL
HEAT EXCH.
HEAT EXCH. BTU
RECOVERY
VENT
WEIGHT
SSVH90-45
32 Sq. Ft.
81,000
95%
3"
205 Lbs.
SSVH130-45
32 Sq. Ft.
110,000
94%
3"
205 Lbs.
SSVH199-80
32 Sq. Ft.
140,000
94%
3"
255 Lbs.
Содержание ANSI Z 21.10.3
Страница 2: ...PAGE 2 ...
Страница 12: ...PAGE 12 ...
Страница 15: ...PAGE 15 ...
Страница 16: ...PAGE 16 ...
Страница 17: ...PAGE 17 ...
Страница 18: ...PAGE 18 ...
Страница 19: ...PAGE 19 ...
Страница 21: ...PAGE 21 Figure 3 A Direct Vent Terminal Clearances per ANSI Z21 10 3 2004 CSA 4 3 2004 ...
Страница 22: ...PAGE 22 ...
Страница 23: ...PAGE 23 ...
Страница 24: ...PAGE 24 ...
Страница 25: ...PAGE 25 ...
Страница 26: ...PAGE 26 ...
Страница 30: ...PAGE 30 PARTS ILLUSTRATIONS ...
Страница 40: ...PAGE 40 ...