W415-2184 / 06.07.19
EN
16
venting requirements
2.6 rear exit - horizontal terminations
0’
10’
10’
15’
15’
19.25’
25’
30’
5’
5’
2 elbow zone
2-3 elbow zone
2-4 elbow zone
2-5 elbow zone
2-6 elbow zone
H
V
V+H ≤ 35 ft. (For longer vent runs, a power
vent is required).
H ≤ 19.25 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
Centre of Base
of Air Collar
17.5’
14” min.
20” max.
0’
1.1’ min.
5.5’
31.1’
20’
14.8’
20’