background image

W415-1710 / B / 08.17.18

EN

72

  

finishing

Under normal conditions, there is no reason to remove the fixed side of the firebox glass door. 

Servicing can be completed from the access side.

note:

FIXED - SEE-THRU ONLY

F. 

Remove GGA from fixed side.

G. 

Remove the screws securing the door to the appliance.

H.  

Tilt the top of the door forward, then lift it up and out of the bottom door retainer.

I. 

When re-installing the door, lift onto the bottom door retainer, tilt the top towards the appliance  

 

and secure with the previously removed screws.

12.8    media tray removal

It is recommended to 

only 

install media trays 

when using sand as media.

 Media trays, where supplied, should 

be stored in the event it is planned to install alternate media at some point in the future.

Natural gas models only:

 

Media should be installed evenly across the burner tray but not directly on the 

burner ports themselves. Never place media directly on the burner ports as this can result in carboning or an un-

appealing flame characteristic. For propane, refer to conversion kit. 

Propane models only:

 

It is recommended 

not

 to install the sand pan media trays for propane applications 

with other media types (i.e glass). Not only will this provide a clean look to the appliance, but it also results in a 

more pleasing and clean burning flame. Media trays should be stored in the event it is planned to install alternate 

media at some point in the future.Media should be installed evenly across the burner tray and a moderate amount 

of media placed on the burner itself and, if necessary, adjusted to achieve a pleasing flame appearance. 

Never 

place excessive media on the burner as this can result in carboning or an unappealing flame charac-

teristic. Never place media in the pilot housing or over the pilot.

 Always check that the appliance ignites 

smoothly across the entire burner to ensure media does not compromise performance. Pay particular attention 

when using power vents to ensure media placement does not affect ignition or flame characteristics. 

All models:

 

Never place media in the pilot housing or over the pilot. Always check that the appliance ignites 

smoothly across the entire burner to ensure media does not compromise performance. To install optional media, 

refer to instruction leaflet included with the media kit.

12.9    optional media placement

Содержание Luxuria Series

Страница 1: ...e gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the supplier Thisappliancemaybeinstalledinanaftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on th...

Страница 2: ...or other flammable material should not be placed on or near the appliance Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Furniture or other objects must be kept a minimum of 4 feet 1 22m away from the front of the appliance Ensure you have incorporated adequate safety measure to protect infants toddlers from touching hot surfaces Even ...

Страница 3: ...outdoor products only this appliance must not be installed indoors or within any structure that prevents or inhibits the exhaust gases from dissipating in the outside atmosphere If applicable the millivolt version of this appliance uses and requires a fast acting thermocouple Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd WARNING Disconnect the appliance main gas valve con...

Страница 4: ...ection 43 7 2 receptacle wiring diagram 43 7 3 in the event of a power failure 43 7 4 battery holder switch installation 44 7 5 initializing the battery holder switch for the first time 44 7 6 wiring diagram 45 7 7 eFire controller application 45 7 7 1 LVX38 50 wiring diagram 46 7 7 2 LVX62 74 wiring diagram 47 7 8 access panel 48 8 0 gas installation 49 9 0 operation 50 10 0 nailing tab installat...

Страница 5: ...be improved if the assembly is warmed using a hair dryer or similar heat source The protective wrap must be removed before operating the appliance This appliance is a decorative product It is not a source of heat and not intended to burn solid fuel This appliance is equipped with a remote control and a wall switch which requires batteries to be installed The remote takes 3 AAA batteries and the wa...

Страница 6: ...500 0 4 500 0 4 500 0 4 500 Max Input BTU HR 38 000 38 000 38 000 38 000 Min Input BTU HR 26 000 31 000 26 000 31 000 P4 45 5 45 5 45 5 45 5 Single Sided See thru Appliance Type LVX62N LVX62P LVX62N2 LVX62P2 Fuel Type Natural Gas Propane Natural Gas Propane Altitude FT 0 4 500 0 4 500 0 4 500 0 4 500 Max Input BTU HR 44 000 38 000 44 000 38 000 Min Input BTU HR 32 000 31 000 32 000 31 000 P4 55 5 ...

Страница 7: ...installation section 7 Install vent shield refer to vent shield installation section 8 Install all electrical wirings refer to electrical information section 9 Install gas lines refer to gas installation section 10 Fit glass guard refer to glass guard assembly installation removal section 11 Test appliance Glass Guard must be installed while testing the appliance 12 Remove and protect glass guard ...

Страница 8: ...plete flexibility in selection of finish materials Ability to place a TV sound bar or artwork above the fireplace The Dynamic Heat Control system relies on an optimized flow of air both through the appliance and the en closure As such the installation of the Dynamic Heat Control system requires certain technical considerations when compared to traditional fireplaces Specifically the Dynamic Heat C...

Страница 9: ...ess the unit is a direct vent sealed combustion product The installation must conform with local codes or in absence of local codes the National Gas and Propane Installation Code CSA B149 1 in Canada or the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the United States Suitable for mobile home installation if installed in accordance with the current standard CAN CSA Z240MH Series for gas equipped...

Страница 10: ... X 4 75 HOLE TO BE 0 250 Ø MATERIAL CLASS III A 2 PERMANENT LABEL WATERPROOF 010MIL VELVET MATTE LEXAN AND OR 050 HI TEMP POLYESTER CAPABLE OF WITHSTANDING A MAXIMUM TEMPERATURE OF 175 F 79 C MIN LETTERING FOR NOT FOR USE WITH SOLID FUEL UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ AVEC CELUI TO BE 10 POINT ARIAL BOLD FACE UPPER CASE AND 2 POINT LEADING SPACING OR EQUIVALENT BLACK LETTERING ON W...

Страница 11: ...iance to the floor for mobile home installation For mobile home installations the appliance must be fastened in place This appliance is certified to be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gase...

Страница 12: ... 57 5 16 1456mm 69 5 16 1761mm 81 5 16 2065mm 93 5 16 2370mm 41 3 16 1046mm 7 1 16 179mm 18 5 8 473mm 3 1 8 80mm 17 3 16 437mm 32 3 4 832mm 39 11 16 1008mm 8 1 16 205mm 8 1 16 205mm Ø 8 203mm Ø 5 127mm GLASS GUARD 1 2 12 7mm A B C Finishing flange depth the finishing flange defines the perimeter of the fireplace opening Framing or finishing materials must NEVER encroach inside the finishing flange...

Страница 13: ...16 1761mm 81 5 16 2065mm 93 5 16 2370mm 2 2 see thru 41 3 16 1046mm 7 1 16 179mm 18 5 8 473mm 3 1 8 80mm 32 3 4 832mm 39 11 16 1008mm 16 3 16 411mm 8 1 16 205mm 8 1 16 205mm Ø 8 203mm Ø 5 127mm GLASS GUARD 1 2 12 7mm 1 2 12 7mm A B C Base of air collar Finishing flange depth the finishing flange defines the perimeter of the fireplace opening Framing or finishing materials must NEVER encroach insid...

Страница 14: ...w mtlfab com Use only Wolf Steel Simpson Dura Vent Selkirk Direct Temp American Metal Amerivent or Metal Fab venting components Minimum and maximum vent lengths for both horizontal and vertical installations clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and must be adhered to For Simpson Dura Vent Selkirk Direct Temp Ameri...

Страница 15: ...ombined These vent kits allow for either horizontal or vertical venting of the appliance The maximum allowable horizontal run is 20 feet 6 1m The maximum allowable vertical vent length is 40 feet 12 2m The maximum number of vent connections is two horizontally or three vertically excluding the appliance and the air terminal connections when using flexible venting A terminal shall not terminate dir...

Страница 16: ...SIDED SINGLE SIDED SEE THRU SEE THRU 3 1 typical venting installation minimum plus rise maximum minimum base of air collar base of air collar D special vent installation periscope termination Use the periscope kit to locate the air termination above grade The periscope must be installed so that when final grading is completed the bottom air slot is located a minimum 12 30 5cm above grade The maxim...

Страница 17: ...EE THRU base of air collar A 6 1 83m minimum vertical rise is considered the minimum practical dimen sion for the specific appliance enclosure and a minimal building structure However a greater minimum vertical rise may be needed to suit the specific application con straints or local codes and or regulatory requirements note ...

Страница 18: ...anda porch or deck N 16 40 6cm 16 40 6cm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without openings Q 3 0 9m 3 0 9m See chart for wider wall dimensions R 6 1 8m 6 1 8m See chart for deeper wall dimensions The terminal shall not be installed on any wall that has an opening between the termin...

Страница 19: ... 2 18 2 1 2 30 38 1 2 462 5 1 elbow zone 1 2 elbow zone 1 3 elbow zone 1 4 elbow zone 1 5 elbow zone 1 6 elbow zone H V V H 40 ft For longer vent runs a power vent is required H 20 ft V H are measured from the centre of vent elbows Elbows are considered as 90º Two 45º elbows One 90º elbow LVX38 LVX50 LVX62 LVX74 SINGLE SIDED LVX38 LVX50 SEE THRU NATURAL GAS ONLY ...

Страница 20: ...1 2 1 1 2 18 4 48 5 1 elbow zone 1 2 elbow zone 1 3 elbow zone 1 4 elbow zone 1 5 elbow zone 1 6 elbow zone H V V H 40 ft For longer vent runs a power vent is required H 20 ft V H are measured from the centre of vent elbows Elbows are considered as 90º Two 45º elbows One 90º elbow 38 1 2 462 LVX62 LVX74 SEE THRU NATURAL GAS ONLY ...

Страница 21: ...H are measured from the center of the vent elbows This example represents a vent that has a maximum of three 90º elbows a combined horizontal vent length H of 10 feet and a combined vertical vent length V of 8 feet 0 0 Base of air collar Base of air collar Since the vent is located in the dark shaded area it is within the acceptable vent configuration 4 3 4 57 NATURAL GAS ONLY ...

Страница 22: ... runs a power vent is required H 20 ft V H are measured from the centre of vent elbows Elbows are considered as 90º Two 45º elbows One 90º elbow ALL APPLIANCES NATURAL GAS ONLY A 6 1 83m minimum vertical rise is considered the minimum practical dimension for the specific appliance enclosure and a minimal building structure However a greater minimum vertical rise may be needed to suit the specific ...

Страница 23: ...ne 1 3 elbow zone 1 4 elbow zone H V V H 40 ft H 10 ft For longer vent runs a power vent is required V H are measured from the centre of vent elbows Elbows are considered as 90º Two 45º elbows One 90º elbow For 0 elbow configurations V is a minimum of 6 to a maximum of 40 6 72 4 3 4 57 Vertical termination only No horizontal termination allowed Refer to appliance specific GPV PVA instructions for ...

Страница 24: ...elbow zone V H 40 ft H 4 ft For longer vent runs a power vent is required V H are measured from the centre of vent elbows Elbows are considered as 90º Two 45º elbows One 90º elbow For 0 elbow configurations V is a minimum of 6 to a maximum of 40 Vertical termination only No horizontal termination allowed Refer to appliance specific GPV PVA instructions for other venting configurations 35 8 102 6 7...

Страница 25: ... air outlet opening Dynamic Heat Control air outlet opening Dynamic Heat Control air outlet opening No materials of any type are permitted in this area Air flow in the shaded area must not be restricted in any way with the exception of an approved appliance vent system No other items are allowed in this area Read Dynamic Heat Control section before proceeding Shaded framing must use non combustibl...

Страница 26: ...th of 3 5 i e one stud If the appliance is recessed further into the enclosure the air flow will be restricted through the DHC system Dynamic Heat Control air outlet opening No materials of any type are permitted in this area Recessed 3 5 max No combustible material allowed Upper frame Upper frame 6 5 max Access side of appliance GLASS GUARD ...

Страница 27: ...ide the necessary air circulation path for the Dynamic Heat Control system Leaving a complete air outlet opening above the enclosure has been found to be well accepted with respect to final appearance and offer minimal distraction It also allows for efficient circulation of air within the room This option offers the simplest method for framing and installation If installing Dynamic Heat Control Pl...

Страница 28: ...rates louvres or other unapproved covers are not permitted and will cause a fire hazard Wall mounted object picture frame appli ance etc ceiling enclosure top must be installed 2 3 0 1 5 Max 6 min Air outlet opening is required to be centered with the appliance ALTERNATIVE Q x R DYNAMIC HEAT CONTROL AIR OUTLET OPEN ING IS HOT WHEN APPLIANCE IS OPERATING Front air outlet opening must be located out...

Страница 29: ...2 1 2 min Increasing the air outlet opening will allow the appliance the glass barrier the temperatures on the surfaces above the fireplace open ing and the enclosure be at cooler temperatures It will also allow the air to circulate more effectively in the room However if the ap pliance is equipped with the Dynamic Heat Control Plus then the opening size must be 80 sq in for models LVX38 and LVX50...

Страница 30: ...n 1 or 2 is not permitted and will overheat the appliance Air outlet opening must be located out of reach of the user Air outlet must not be restricted by furnishings or decor Wall mounted object picture frame appli ance etc ABSOLUTELY NO OBSTRUCTION OR RESTRICTION ALLOWED IN THE ENTIRE SHADED AREA WITH THE EXCEPTION OF APPROVED VENTING Option 4 is similar to option 1 with the addition of a hard c...

Страница 31: ...ty Do not notch the framing around the appliance stand offs Failure to maintain air space clearance may cause over heating and fire Prevent contact with sagging or loose insulation or framing and other combustible materials Block opening into the chase to prevent entry of blown in insulation Make sure insulation and other materials are secured Minimum clearance to combustibles must be maintained o...

Страница 32: ... 8 320 4cm 1 2 54cm min 6 15 2cm min minimum framing Horizontal vent sections A minimum clearance of 3 76mm on the top outside of the enclosure and 2 51mm on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to com bustibles is required Horizontal vent sections within enclosures require a minimum clearance of 6 152mm at the top of the vent pipe Vertical ...

Страница 33: ... 4cm 91 231 1cm 91 231 1cm Horizontal vent sections A minimum clearance of 3 76mm on the top outside of the enclosure and 2 51mm on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to combustibles is required Horizontal vent sections within enclosures require a minimum clearance of 6 152mm at the top of the vent pipe Vertical vent sections A minimum of ...

Страница 34: ...3 76mm on the top outside of the enclosure and 2 51mm on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to combustibles is required Horizontal vent sections within enclosures require a minimum clearance of 6 152mm at the top of the vent pipe Vertical vent sections A minimum of 1 25mm all around the vent pipe on all vertical runs to combustibles is re ...

Страница 35: ...31 1cm E J F E F J L L Before framing the appliance ensure to install the firestop first as it will not fit between the studs if installed after framing Before framing the appliance ensure to install the firestop first note The LVX series requires a minimum enclosure height as illustrated dimension L mea sured from the bottom of the appliance For temperature requirements this area must be left uno...

Страница 36: ... touch the vent pipe Remove insulation to allow for the installation of the attic shield and to maintain clearances to combustibles Do not fill the space between the vent pipe and enclosure with any type of material Do not pack insulation or combustibles between ceiling firestops Always maintain specified clearances around venting and firestop systems Install wall shields and firestops as specifie...

Страница 37: ...ther Figure 4 2 Ensure both ends line up and secure ends with clip and fasteners Figure 5 Fig 4 Fig 5 Fig 6 3 Insert the vent sleeve tabs into the firestop spacer slots then bend the tabs over to secure to the firestop spacer along with 4 supplied fasteners Figure 6 Note orientation of dimples and standoffs note ...

Страница 38: ...r up the open end of the shield and tighten This will prevent any materials such as insulation from filling up the 1 25mm air space around the pipe Caulking Vent Pipe Shield Vent Pipe Shield Vent Pipe Collar Firestop underside of joist 10 3 4 273mm 10 3 4 273mm 16 3A This application occurs when venting through an exterior wall Having determined the correct height for the air terminal location cut...

Страница 39: ...the vent pipe a minimum of 2 50 8mm over the inner sleeve of the air terminal and secure with a minimum of 3 screws B Using the outer flex pipe slide over the outer combustion air sleeve of the air terminal and secure with a minimum of 3 screws Seal using red RTV silicone W573 0002 not supplied C Insert the vent pipes through the firestop maintaining the required clearance to combustibles Holding ...

Страница 40: ...Make weather tight by sealing with caulking Where possible cover the sides and top edges of the flashing with roofing material F Aligning the seams of the terminal and air terminal connector place the terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal Secure with a minimum of three screws when 4 7 5 8 and 3 5 venting is used and a minimum of six s...

Страница 41: ...SCREWS Vertical installations may display a very active flame If this appearance is not desirable the exhaust outlet may be restricted with a Wolf Steel approved restrictor kit This kit is not recommended for short vertical vent runs Depending on the model and or year of your appliance mounting holes may not exist 6 6 restricting vertical vents 6 6 1 LVX38 LVX50 6 6 2 LVX62 LVX74 A If mounting hol...

Страница 42: ...ld to its maximum vertical Figure 2 3 Tighten the fasteners to lock the vent shield height Figure 3 4 Remove the fasteners as shown Figure 4 DO NOT DISCARD FASTENERS 5 Align the vent shield with the holes and replace above screws Figure 5 6 Secure the vent shield with two fasteners supplied to the front upper frame Figure 6 note 6 7 vent shield installation Fig 4 Fig 5 Fig 6 SEE THRU EXAMPLE 1 x2 ...

Страница 43: ...ent of a power failure If the battery holder switch is equipped with batteries the appliance will still have ON OFF functions during a power failure Refer to operation section in the Owner s manual when communications between battery holder switch and remote have been lost The battery holder switch will emit a beep sound to confirm programming has been successful once power is restored During a po...

Страница 44: ...lder note the polarity of the batteries and insert as indicated on the cover B Ensure the 3 position slider switch is switched to the REMOTE position middle position C Press the reset programming button use a small object such as a paper clip in order to reach the button marked PRG as shown in the illustration below D The battery holder will beep 3 times to indicate that it s ready to synchronize ...

Страница 45: ...s your current mood or your décor with ease the simple colour wheel tool swiftly scrolls through the full color spectrum Napoleon s eFIRE app controls every function of your fireplace including on off flame height and a timer to create a schedule for your fireplace that works for you Using the instructions on the eFIRE controller application website http napoleonfireplaces com efire install the ap...

Страница 46: ...ITCH W750 0294 BLUETOOTH W190 0090 W190 0125 LED CONTROLLER COMMAND SENSE LED WIRE 8 LED WIRE MV TRANSFORMER W707 0019 LED LIGHTS W750 0358 LIGHT BLOWER PIGTAIL W707 0019 W750 0429 W750 0423 ACCENT LIGHTS W750 0424 WIRE HARNESS W750 0276 WIRE HARNESS W750 0317 EXTENSION W350 0655 W405 0049 W750 0435 BT WIRE HARNESS W750 0433 W750 0401 GROUND 7 7 1 LVX38 50 wiring diagram ...

Страница 47: ... COMMAND SENSE LED WIRE R LED WIRE L TRANSFORMER W707 0019 LED LIGHTS W750 0358 LIGHT BLOWER PIGTAIL W707 0027 ACCENT LIGHTS W750 0317 EXTENSION W750 0435 BT WIRE HARNESS W750 0433 W750 0401 W405 0049 W750 0422 LIGHT WIRE HARNESS BLUE CONNECTORS RED CONNECTORS TERMINAL BUS W060 0008 W350 0655 GROUND W660 0204 HIGH LIMIT SWITCH W750 0424 WIRE HARNESS W750 0276 WIRE HARNESS 7 7 2 LVX62 74 wiring dia...

Страница 48: ...fied service technician immediately to have the appliance inspected for damage to the electrical circuit Risk of electrical shock or explosion Do not wire 110V to the valve or to the appliance wall switch Incorrect wiring will damage controls All wiring should be done by a qualified electrician and shall be in compliance with local codes In the absence of local codes use the current CSA22 1 Canadi...

Страница 49: ...ition and secure If equipped with a flex connector the appliance is designed to accept a 1 2 13mm gas supply Without the connector it is designed to accept a 3 8 9 5mm gas supply The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance Connect the gas supply in accordance to local codes In the absence of local codes install to the current CAN CSA B149 1 In...

Страница 50: ...l switch to the appliance J If the appliance will not operate follow instructions TO TURN OFF GAS and call your service technician or gas supplier A Set thermostat to lowest setting if equipped B Turn off the remote wall switch to the appliance C Turn off all electric power to the appliance if service is to be performed D Turn manual shutoff valve clockwise to the OFF positon Do not force Turn off...

Страница 51: ...NOT DISCARD ALIGN THE NAILING TAB WITH THE HOLES ON THE APPLIANCE SECURE WITH THE SCREWS FROM STEP 1 SECURE WITH SCREW SUPPLIED IN THE MANUAL BAGGIE TO THE UPPER FRONT FRAME TO INSTALL NAILING TABS FOR SEE THRU APPLIANCES REPEAT STEPS WITH THE OPPOSITE SIDE 10 0 nailing tab installation 1 x2 If the front frame was removed it must be reinstalled prior to installing the nailing tabs important ...

Страница 52: ...nal Appliance does not need to be elevated above floor L 73 185 4cm 73 185 4cm 91 231 1cm 91 231 1cm Q 2 min and 3 max Q x R 80 sq in 160 sq in minimum framing Drywall Insulation Ceiling K R E F J L Q Option 2 illustrated appliance not shown Finish framing must be built after appliance has been placed in its final position and venting connected note ONLY APPLICABLE TO OPTION 2 AND 3 Opening must b...

Страница 53: ...sions represent finished sizes and where applicable should be adjusted to include finish material thickness Can only be increased to 4 max by building a protrusion Max 21 53 5cm Insulation Drywall Ceiling K R E F J L M Q minimum framing Finish framing must be built after appliance has been placed in its final position and venting con nected This configuration also re quires recess area to use non ...

Страница 54: ...1 1cm F 53 13 16 136 7cm 65 13 16 167 2cm 77 13 16 197 6cm 89 13 16 228 1cm J Optional Appliance does not need to be elevated above floor L 73 185 4cm 73 185 4cm 91 231 1cm 91 231 1cm Q 2 min and 3 max Q x R 80 sq in 160 sq in Ceiling K R E F J L Q Drywall Finish framing must be built after appliance has been placed in its final position and venting connected note The LVX series requires a mini mu...

Страница 55: ...ming must be built after appliance has been placed in its final position and venting connected When finished protrusions must never encroach inside the appliance finishing flange as this will impede the fitment of the barrier and safe operation See finishing section in the installation manual note note Insulation Drywall This is a recommended dimension when mounting electronics above the appliance...

Страница 56: ...e opening surrounding the door as this will interfere with the doors ability to relieve pressure 12 0 finishing WARNING 12 1 fastener placement restriction 1 1 2 8 2 G a s V a l v e No fasteners permitted with greater than 3 4 penetration into appliance No fasteners permitted When securing non combustibles we suggest using high temperature construction adhesive within 2 5 08cm above and to the sid...

Страница 57: ...reases the operating temperature of the appliance and around the appliance opening This is counterproductive when trying to demon strate the benefits of heat management to potential customers In extreme cases the appliance may become hot enough for the high limit switch to shut down the appliance The outside of the enclosure must be finished on all four sides and must include a complete floor note...

Страница 58: ...n Air outlet opening must be located out of reach of the user Air outlet opening must not be restricted by furnishings or decor SHADED AREA MUST BE NON COMBUSTIBLE MATERIALS Recessed installation requires recess material to use non combustible facing due to close proximity to vent Air outlet opening must be located out of reach of the user Air outlet opening must not be restricted by furnishings o...

Страница 59: ... the frame around the glass guard assembly frame must not project more than 4 10cm from the face of the glass guard above the door and sides only WARNING SAFETY BARRIER finishing flange all around SIDE VIEW 4 10cm Max 4 10cm Maximum protrusion must not encroach on finishing flange SAFETY BARRIER 1 25mm 2 51mm Non combustible protrusion Glass Guard ...

Страница 60: ...mantel clearances 25 11 16 65 2cm 2 5 1cm 2 5 1cm 12 30 5cm max MANTEL HEIGHT MANTEL DEPTH Bottom of finishing flange Optional hearth extension no depth restric tion Risk of fire Maintain all specified air space clearances to combustibles Failure to comply with these instructions may cause a fire or cause the appliance to overheat Ensure all clearances i e back side top vent mantel front etc are c...

Страница 61: ...available to finish your installation The trim kit can be painted as an accent colour or to blend in with room decor The minimum air opening area must be maintained after the finishing material has been installed Contact your local authorized dealer for more information 12 5 optional trim finishing The inner surfaces may be visible note ...

Страница 62: ...ily fitted and adjusted before finish framing and finishing the appliance It is much easier to make adjustments with the appliance pre finishing access panel removed It is recommended that the GGA is removed after preliminary adjustment and stored safely in the original packaging whilst finishing is complete Take precautions to protect the appliance during finishing Key Components Horizontal tab N...

Страница 63: ...f their slots it may be necessary to loosen the latch securing screws and slide them all the way down Retighten the latch securing screws loosely taking care not to overtighten Fig 4 Repeat for other end of GGA note DO NOT OVERTIGHTEN Fig 3 1 Unpack the GGA and keep packaging materials to store the GGA after test fitting Access panel Control cover Door trim GGA Latch Latch bracket mounting screws ...

Страница 64: ...arefully hook GGA onto GGA slider brackets by aligning the horizontal tabs on the GGA with the horizontal slots in the bottom of the GGA slider brackets and moving the GGA back into the GGA slider brackets A Ensure both top and bottom tabs of the GGA engage with hooks of the GGA slider brackets B Fig 5 7 Install 2 vertical adjustment screws underflush of GGA slider bracket surface C Fig 6 ...

Страница 65: ...or bottom Repeat on other end of GGA Gap Horizontal adjustment screws installed unevenly and or prematurely No gap Fig 11 Fig 10 Fig 10 Fig 8 Fig 7 8 The GGA mount bracket holes should be lined up with the screw holes of the GGA slider brackets to ensure a clear line of sight Fig 8 It is typically necessary to raise the GGA on both sides using the vertical adjustment screws Raising the GGA approxi...

Страница 66: ... to hold GGA against GGA slider bracket Do not fully tighten until adjustment is complete and during final GGA installation 10 The GGA catches should be installed toward the appliance It may be necessary to loosen the GGA catch securing screws on the bottom of both sides of the GGA and slide them all the way towards the back of the GGA Retighten securing screws Fig 13 Outer glass Fig 12 GGA catch ...

Страница 67: ...l gasket as it becomes warm when the appliance is operating It is REQUIRED to have the gasket touching both ends of the outer glass Intermediate Glass Fig 15 WARNING Normally there is no need to adjust the position of the heat rail Contact your authorized Napoleon dealer before attempting any adjustment of the heat rail Fig 14 Heat rail with gasket 11 Slide the GGA into the appliance until outer g...

Страница 68: ...al is not installed plumb and square it may be necessary to make final horizontal GGA adjustments after finishing note 12 Check if the GGA plane is straight Adjust with horizontal adjustment screws on both ends if necessary Fig 16 13 Check if the latches are correctly positioned Fig 17 Adjust latches if necessary Retighten the screws securely but do not overtighten ...

Страница 69: ...ould be negligible The GGA should unlatch smoothly without the need for excessive force Continue to adjust the GGA catches and or latches until the GGA can be moved correctly Tighten all screws securely but do not overtighten note For see thru models repeat instructions for second GGA to be installed on the fixed side 17 Remove GGA see to remove GGA section and safely store the GGA after prelimina...

Страница 70: ...engages from GGA Pull gently on GGA while releasing the latch 2 Pull both sides of GGA keeping it parallel to the appliance 3 Remove the screws and washers securing the GGA to the GGA slider brackets 1 per corner 4 total 4 Carefully lift the GGA up and off the GGA slider brackets 2 per side Set assembly on a clean soft surface Care must be taken to protect the edges of glass ...

Страница 71: ...glass door installation removal Door trim Side view Door trim Door frame LVX38 Illustrated Ensure to leave one hand on the glass door during entire door removal note C For door removal locate the top and bottom door latches Pull latches forwards and away to disengage door latches LVX38 Illustrated Ensure the door opens freely and closes sealed note IMPORTANT Once latches are engaged test to make s...

Страница 72: ...It is recommended not to install the sand pan media trays for propane applications with other media types i e glass Not only will this provide a clean look to the appliance but it also results in a more pleasing and clean burning flame Media trays should be stored in the event it is planned to install alternate media at some point in the future Media should be installed evenly across the burner tr...

Страница 73: ...lass ensure that it is dry If replacing use only the replacement glass media available from your local authorized dealer distributor Glass media over the burner ports will cause flame lifting and sooting problems Do not place any media glass or vermiculite in or around the pilot opening and or on the burner ports This will interfere with the pilot operation Pilot Area If media trays are not requir...

Страница 74: ...or warranty replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appliance Installation date of appliance Part number Description of part Finish Parts part numbers and availability are subject to change without notice Parts identified as stocked will be delivered withi...

Страница 75: ...4 W010 3554 W010 3554 W010 3554 Yes 6 High Limit Switch W660 0204 W660 0204 W660 0204 W660 0204 Yes 7 Napoleon Logo W385 2010 W385 2010 W385 2010 W385 2010 Yes 8 Heat Rail w gasket W010 4257 SER W010 4258 SER W010 4259 SER W010 4260 SER Yes 9 Media Tray W710 0104 SER W710 0107 SER W710 0099 SER W710 0098 SER 10 Porcelain End Panel W475 1031 BK2GL SER W475 1031 BK2GL SER W475 1031 BK2GL SER W475 10...

Страница 76: ...W415 1710 B 08 17 18 EN 84 replacement parts 15 2 burner components Items may not appear exactly as illustrated 1 2 3 4 5 6 7 8 9 10 11 12 13 14 16 19 20 21 22 23 25 26 27 28 29 18 17 15 24 ...

Отзывы: