installation planning
4.0 installation planning
!
WARNING
• Do
NOT
cover or place any items in the
Dynamic Heat Control™
air outlet. Failure to comply with these
instructions will create a fire hazard.
• Ensure a
ir flow within the air passage is not restricted in any way with the exception of approved venting.
enclosure top
and/or ceiling
Dynamic
Heat
Control™
air
outlet opening
3”
Header
Standoff
Upper
Frame
Combustible
studding MUST
not be used past
the dotted line
Dynamic
Heat
Control™
air outlet
opening
Dynamic
Heat
Control™
air outlet
opening
Dynamic
Heat
Control™
air
outlet opening
No materials of any type
are permitted in this area
Air flow in the shaded area
must
not be restricted in any way with the exception of an approved appliance vent
system. No other items are allowed in this area.
Read Dynamic Heat Control™ section before proceeding.
Shaded framing
must
use non-combustible materials.No combustible materials allowed in this area or the space
between studs (i.e. no wiring, conduits, electrical bores, combustible framing members, AV equipment, finishing
brackets, framing, etc.)
*Restrictions also apply to see-thru when one or more recess is used.
Single-Sided
Single-Sided
(Recessed)*
See-thru