finish framing - after appliance installation
11.0 finish framing
- after appliance installation
Appliances can be built in with combustible framing and finishing unless stated.
There are various methods to ventilate the enclosure. Refer to “Dynamic Heat Control™” and “installation
planning” sections.
The appliance must be installed at this point of framing. Appliance is not shown to better illustrate finish framing.
note:
11.1 framing with Dynamic Heat Control™
single-sided flush
Ref
LVX38
LVX50
LVX62
LVX74
K
39 15/16” (101.4cm)
39 15/16” (101.4cm)
39 15/16” (101.4cm)
39 15/16” (101.4cm)
E**
18” (45.7cm)
18” (45.7cm)
18” (45.7cm)
18” (45.7cm)
F
53 13/16” (136.7cm)
65 13/16” (167.2cm)
77 13/16” (197.6cm)
89 13/16” (228.1cm)
J
Optional - Appliance does not need to be elevated above floor
L
73” (185.4cm)
73” (185.4cm)
91” (231.1cm)
91” (231.1cm)
Q*
2” min and 3” max
(Q x R)*
80 sq. in.
160 sq. in.
minimum framing
Drywall
Insulation
Ceiling
K
R
E
F
J
L
Q
Option 2 illustrated (appliance not shown)
Finish framing
must
be built after
appliance has been placed in its final
position and venting connected.
note:
* ONLY APPLICABLE TO OPTION 2 AND 3 - Opening
must
be centered in enclosure on appliance. Dimensions represent
finished sizes and where applicable should be adjusted to include finish material thickness.
**Max. 21” (53.5cm).
The LVX series requires a minimum
enclosure height, as illustrated (dimen-
sion L), measured from the bottom
of the appliance. For temperature
requirements, this area must be left
unobstructed. Some venting con-
figurations that require more vertical
rise will require a larger enclosure to
provide minimum vertical clearance
between vent pipes and combustibles.