installation planning
4.4 installation option 4 - open enclosure with hard combustible valance
ceiling
4” min
air outlet opening
must be continuous
around enclosure top.
6” Max.
6” Min.
6” Min.
ALTERNATIVE
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
NOTE: Air outlet opening must be at least continuous
around the top of the enclosure for a valance to be permit-
ted. Using the minimum air outlet opening from option 1 or 2
is not permitted and will overheat the appliance.
Air outlet opening must be located out of reach of the user.
Air outlet
must
not be restricted by furnishings or decor.
Wall mounted object
(picture frame, appli-
ance, etc.)
ABSOLUTELY NO OBSTRUCTION OR RESTRICTION
ALLOWED IN THE ENTIRE SHADED AREA WITH THE
EXCEPTION OF APPROVED VENTING
Option 4 is similar to option 1 with the addition of a hard combustible valance. Minimum opening dimensions and valance
dimensions
must
be followed (see option 4 diagram).
Restricting air movement within the valance area will overheat the
appliance, the enclosure, and finishing material.
NOT Suitable for Dynamic Heat Control™ Plus