4
W415-0807 / C / 09.02.16
2.1 DIMENSIONS
35 1/2"
902mm
33"
838mm
5 1/2"
140mm
3"
76mm
GAS
INLET
37 3/8" 949mm
27" 686mm
12 1/4"
311mm
13 1/4" 337mm
2.2 GENERAL
INSTRUCTIONS
4.3B
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER
to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
•
The appliance off valve must be a “T” handle gas
cock.
• The
fl exible connector must not be longer than 36”
(914.4mm).
The installation must conform with local codes or, in absence
of local codes, the National Gas and Propane Installation
Code CSA B149.1 in Canada, or the National Fuel Gas
Code, ANSI Z223.1 / NFPA 54 in the United States.
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certified in the U.S.
by the National Fireplace
Institute
® (NFI) as NFI Gas
Specialists
www.nficertified.org
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” (1219.2mm)
FROM THE FRONT FACE OF THE APPLIANCE.
FIRE RISK. EXPLOSION HAZARD.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TEST-
ING GAS LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE
PRESSURE TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH
THIS APPLIANCE. USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS
COMPONENTS, VENTING COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL
VOID THE WARRANTY AND CERTIFICATION.
THE APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS INDICATED ON THE RATING PLATE.
THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES.
!
WARNING
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The appliance must be
isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the appliance is installed directly on combustible material other than wood fl ooring, the appliance shall
be installed on a metal or wood panel extending the full width and depth.
Содержание GSS36N
Страница 22: ...22 W415 0807 C 09 02 16 13 0 NOTES 44 1...
Страница 23: ...23 W415 0807 C 09 02 16 44 1...
Страница 46: ...13 0 NOTES 44 1 46 W415 0807 C 09 02 16...
Страница 47: ...44 1 47 W415 0807 C 09 02 16...