NAPCO GEM-ACM1D Скачать руководство пользователя страница 5

or outside the secured area and is used in conjunc-
tion with a proximity card (enabled for arming) pre-
sented at a card reader.  When the RTA button is 
pressed, a window of time is created during which a 
valid card must be presented to the card reader in 
order for arming to take place.  This window of time 
is equal to six times (6x) the time programmed in the 
"Un-Lock" time (see pages 11 and 16)  The RTA 
button is a normally open momentary switch wired 
between terminals 28 and 29.  Before arming, the 
area to be armed must be secured (all protected 
doors closed, all motion sensors stable, etc.).   

Note:

  Consult all installation instructions provided with 

each accessory before installation and connection to 
the GEM-ACM1D. 

 

5.  Connect  Card  Reader(s).

  Each GEM-ACM1D can 

control one access card reader and two when used with 
a GEM-2D module.  Card readers can be installed on 
one door (to control both entry and exit) or when used 
with the GEM-2D on two separate doors (to control ac-
cess in one direction only).  Connect the Card Readers 
to the GEM-ACM1D as shown in the table below.  

Note:

  Connecting the power lead of a 5VDC reader to 

a 12VDC configured power terminal may damage the 
card reader.  See "Card Reader Power Jumper" further 
in this manual for proper power configuration.   

 

      Each ACM will operate with any card reader that trans-

mits data in a Weigand format, regardless of manufac-
turer.  Two card formats are supported:  (1) NAPCO 
standard 36 bit format or (2) HID standard 26 bit format.  
The "embossed" number printed on the face of the 
card, up to 6 digits, must be manually entered as the 
user code (see Programming pages 12 and 18).  When 
this embossed number is entered and configured in the 
system, the number cannot be entered at a system key-
pad for access.   

 

Reader LED Indications 

      Many card readers include an LED for visual feedback 

when access cards are presented to the reader.  See 
Table 3 for the variety of LED indications and their 
meanings. 

 
 
 
 
 
 
 
 
 
 

Remote Status LED's (Optional) 

      Some card readers provide LED's that can be wired to 

indicate system status.  For readers with a snap-on 
bezel and red and green LED's, wire to terminals 30 
and 31 (door 1) and terminals 48 and 49 (door 2).   

 
 

 
 
 
 
 
 
 
 
 
      When Stealth Mode is enabled, the LED indications 

are displayed for one minute only.  See Stealth Mode 
section on page 10 below.  When Stealth Mode is 
disabled ("normal operation"), the LED's are always 
enabled and mimic the Keypad Status LEDs for the 
following functions only:  Armed, Disarmed, Ready, 
Not-Ready and Alarm.   

 

Card Reader Sounder Operation 

      Many card readers include a sounder for audible feed-

back.  The sounder output can be connected to local 
warning devices for: 

 

Access Door Kick-In

.  Kick-In occurs when a locked 

access door is opened (the n/c circuit between termi-
nals 25-26 or 43-44 opens).  A "Kick-In" can also oc-
cur if either door circuit is shorted while locked (a su-
pervisory resistor should be connected as close to 
the door contact as possible, as required for Grade A 
installations).  The Sounder Out terminals 23 and/or 
41 turns active low, and the local sounder activates 
and remains active until the access door is closed.   

    Additionally the "Kick-In" condition will cause the 

GEM-X255 connected to the GEM-ACM1D to sense 
the zone programmed "Kick-In Zone" as faulted.  De-
pending on the panel program, a faulted "Kick-In 
Zone" will generate an alarm or trouble.  Typically, 
this zone would be programmed for 24-hour and Bur-
glary output.  The panel will continue to sense this 
zone as open until the door contact is restored.   

Door Ajar

.  The access door is open for 30 seconds 

or longer.  The local sounder activates and remains 
active until the door is closed.   

    A "Door Ajar" condition causes the GEM-ACM1D to 

turn the (-) SND OUT (terminal 23) active low.  Typi-
cally, this activates the card reader sounder.  A re-
mote low current sounder may be wired to the SND 
OUT and (+) READER PWR (terminal 17), but be 
aware that the sounder will activate whenever the 
GEM-ACM1D uses the SND OUT terminal to gener-
ate sounds on the card reader (valid card, RTE but-
ton press, first swipe of double swipe arm, etc.).  The 
SND OUT will remain on until the door is closed or 
until the SND OFF button is pressed.  (The SND OFF 
button is a N/O momentary push button wired to ter-
minals 24 and 25 of the GEM-ACM1D). 

    Additionally the "Door Ajar" condition will cause the 

GEM-X255 connected to the GEM-ACM1D to sense 
the zone programmed "Door Ajar Zone" as faulted.  
Depending on the panel program, a faulted "Door 
Ajar Zone" will generate an alarm or trouble.  The 
panel will continue to sense this zone as open until 

INST

A

L

L

A

T

ION/
M

OUNTING INSTRUCTIONS 

Table 3:  Reader LED Indications 

LED INDICATION 

ACCESS CONDITION 

Steady Red 

Door Locked 

Short Steady Green 

Card Read--Invalid card or 

disabled user 

Alternating Green and Red 

(Downloading PCD-Windows 

Program to ACM) 

Long Steady Green 

Card Read--Valid card, user 

enabled (door unlocked) 

Table 3a:  Remote Status LED's 

LED INDICATION 

SYSTEM CONDITION 

Steady Red 

System Armed 

Red LED is off 

System Disarmed 

Blinking Red 

System in Alarm 

Steady Green  

System Ready to Arm  

Green LED is off 

System Not Ready to Arm 

Содержание GEM-ACM1D

Страница 1: ...ng a locking device such as a magnetic lock or electric strike when the proper credential is presented to the card reader Access control is integrated with the bur glary functions of the GEM X255 It can be used to arm and disarm the system annunciate and report alarms and troubles and monitor the access door without the need for additional contacts Up to 4 GEM ACM1D modules may be connected to a G...

Страница 2: ...2 24 gauge wire is recommended for all connections be tween the panel and the GEM ACM1D and 18 gauge wire for all door strikes Avoid running wires parallel to other types of wiring that can cause electrical interference Typical Installations There are two basic ways the GEM ACM1D may be in stalled to provide access control both are described be low Option 1 uses a single card reader on the exterio...

Страница 3: ...irectly to the GEM ACM1D Do not use wireless contacts e Optional accessories such as an egress button au dible silence button etc should be mounted inside the restricted area 3 Install Tamper Switches J1 must be cut to enable tamper Normally open tamper switches not supplied can be installed in the front and back of the cabinet to provide protection from unauthorized entry The tamper switches are ...

Страница 4: ...by schedules pro grammed into the panel These door lock outputs can operate DC powered locking devices such as magnetic door locks or other electromechanical locks and can be configured to operate in Fail Secure which remain locked when power fails or Fail Safe which unlock when power fails configurations For normally de energized door locks connect ground to terminal 4 wire terminal 3 to terminal...

Страница 5: ...ly Armed Disarmed Ready Not Ready and Alarm Card Reader Sounder Operation Many card readers include a sounder for audible feed back The sounder output can be connected to local warning devices for Access Door Kick In Kick In occurs when a locked access door is opened the n c circuit between termi nals 25 26 or 43 44 opens A Kick In can also oc cur if either door circuit is shorted while locked a s...

Страница 6: ...PWR and D2 PWR outputs Jumper JP3 will not affect the battery standby operation of all other terminals on the GEM ACM1D Therefore if AC power is lost the GEM ACM1D will continue to function but doors will not be powered unless powered by a separate circuit When this jumper is not installed the GEM ACM1D fulfills the UL 4 Hour Standby requirement and is allowed to re main a UL listed mercantile bur...

Страница 7: ...he installation of electrically separate panic hardware to ensure the door can be opened in the event of an emergency Door strike outputs are controlled by schedules pro grammed into the panel These door strike outputs can operate DC powered locking devices such as magnetic door locks or other electromechanical locks and can be configured to operate in Fail Secure which remain locked when power fa...

Страница 8: ...nals When AC power is removed these ter minals will not have battery standby voltage available UL has only evaluated the system with JP3 removed In addition this Standby Battery Chart has not been evaluated by UL 1 STANDBY CURRENT STANDBY CURRENT Amps DEVICE QTY EACH TOTAL GEM ACM1D 1 X 0 04 0 04 GEM 2D 1 X Reader 2 of 2 X Door Strike 1 X Door Strike 2 X X X X TOTAL STANDBY CURRENT Amps Reader 1 o...

Страница 9: ...door For each door programmed there are three possible events that can occur and thus activate the zone specified You MUST designate a separate zone number for each of the three possible events below Zone Assign a zone number to activate when the access door is opened wired to door contacts Forced Entry Zone Assign a zone number to acti vate when a door is opened but not unlocked Door Ajar Zone As...

Страница 10: ...ust be presented twice within the time specified in the Two Swipe Arm Time detailed on page 11 Corresponds to GEM X255 address 2780 bit 0 press 1 on the keypad Enable Napco Proprietary Access Format The GEM ACM1D or GEM 2D supports two proximity card formats 1 NAPCO standard 36 bit proprietary format or 2 HID standard 26 bit format Check to allow the GEM ACM1D or GEM 2D to recognize this standard ...

Страница 11: ...valid and enabled user the GEM ACM1D energizes the D1 Relay which either removes power or sup plies power to the door lock unlocking the lock The lock will remain unlocked for the programmed Un Lock Time If the door is not opened as sensed by the door contact by the end of the Un Lock Time the lock power is reapplied removed re locking the door until another programmed card credential is pre sente...

Страница 12: ...mn and the ACM Area column are mutually exclusive either can be used but not both with one user row The Area column assigns the keypad user code to an area To assign the user to an ACM Area see ACM Area section below Click the drop down box to display the areas and click each area to highlight and select ACM Area Assign a user and their assigned prox imity card to an ACM area Click the drop down b...

Страница 13: ...ith other sched uled restricted time if needed Date Enter the dates of the week you wish to include with the previously programmed Normal Time For example the user who works 9AM 5PM Monday through Friday click in the Date column of the schedule you are changing the Date Schedules window opens Click Day of Week drop down box and click to highlight the days you wish to include IMPORTANT After adding...

Страница 14: ...mapped to the access doors will indicate faulted E54 000 LOW BATT NO AC Power failure for ACM 1 Check power transformer Check for blown fuse or cir cuit breaker general power outage Also may indicate battery below 11 volts If battery not recharged within 24 hours replace it E55 000 LOW BATT NO AC Power failure for ACM 2 Check power transformer Check for blown fuse or cir cuit breaker general power...

Страница 15: ...to enter the Address Program Mode Address 0000 will display 4 Press the 4 digits of the address listed below The existing data will display and the cursor will advance to the data field 5 Program the address as required 6 Press U to save 7 Enter another 4 digit address to continue programming or press C to exit and resume normal keypad operation KEYPAD 1 For ease of programming it is recommended t...

Страница 16: ...5 6 7 8 ACM 1 Door 1 2784 ACM 1 Door 2 2785 ACM 2 Door 1 2786 ACM 2 Door 2 2787 ACM 3 Door 1 2788 ACM 3 Door 2 2789 ACM 4 Door 1 2790 ACM 4 Door 2 2791 Default blank blank from address 2784 2791 ADDR ACM DOOR AREA OPTIONS ADDRESS 2784 2791 ACM DOOR AREA OPTIONS 1 Select the desired option entering the option number 1 3 for each address 2 Enter corresponding option number in address location NOTE D...

Страница 17: ...ss U or D to save ENABLE PANEL OPTIONS ADDRESS 2423 ENABLE PANEL OPTION 1 Select the Panel Option from the table shown and enter in the corresponding address location above 2 Press U or D to save Scheduled Free Access Index ADDR ACM 1 Door 1 4072 ACM 1 Door 2 4073 ACM 2 Door 1 4074 ACM 2 Door 2 4075 ACM 3 Door 1 4076 ACM 3 Door 2 4077 ACM 4 Door 1 4078 ACM 4 Door 2 4079 Default blank blank from ad...

Страница 18: ...Y Y Y C Y Y D Y Y Y E Y Y Y F Y Y Y Y NONE Note These entries are only available when address 3905 bit 7 is enabled Example Enter a code of 123456 as 123456 from left to right ACM ZONE OPTIONS Enter the Zone numbers in two digit hexadecimal format for each option in the table below The left digit nibble determines the type of device for Keypad and 1 for ACM The right digit nibble determines the ho...

Страница 19: ...19 Name Embossed Card Number Facility Code Access Level Code Type ACM Area Access Group Access Control User s Chart ...

Страница 20: ... 01 09 45AM A1D1U195 KP Display NONE GEM PRINT 01 08 04 21 45 ACM 1 Access Denied to User 195 903466 via Door 1 If the card is not in database the user will be logged as User 0 Event AC Fail Low Battery Restore Burg Log 01 08 04 09 45 PM ACM Power Restore ACM 1 Power Trouble ACM Log 01 08 04 09 45 PM ACM Power Restore ACM 1 Power Trouble KP Log ACMPwrTrbR 01 08 09 45PM ACM1 KP Display NONE GEM PRI...

Страница 21: ... PM Close Area 1 User 195 ACM Log NONE KP Log Close 01 08 A1 U010 KP Display NONE GEM PRINT 01 08 04 21 45 Close Area 1 User 195 Event Scheduled Free Access Activated Burg Log 01 08 04 09 45 PM External Relay 1 ON ACM Log NONE KP Log Relay On 01 08 09 45PMR001 KP Display NONE GEM PRINT 01 08 04 21 45 External Relay 1 ON This event occur even when no external relay board present on the system Event...

Страница 22: ...22 NOTES ...

Страница 23: ...23 ...

Страница 24: ...on purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be liable for an amount in excess of NAPCO s original selling price of the product for any loss or damage whether direct indirect incidental consequential or otherwise arising out of any failure of the product Seller s warranty as hereinabove se...

Отзывы: