Technical
Manual
SMCI36
Troubleshooting
Issue: V 1.0
25
Possible errors in CANopen mode
Error Possible
cause
Elimination
The wrong node ID has been
set.
On the <Configuration & NMT> tab
in NanoCAN, select the node ID that
is set on the rotary switches of the
controller.
Wrong baud rate setting.
On the <Configuration & NMT> tab
in NanoCAN, select the baud rate
1000 kbps.
No
communication
with the
controller
The communication cable is
not connected or is
interrupted.
Check all connections, especially the
terminal resistances.
Transmission
fault
Data transmission is disturbed
(sporadically).
Switch the power supply off and on
again.