NED 6LC - NED 350L
Power on
The condensate drain is powered on.
L1
The green and red LED flash one after the other for 5 seconds.
L2
P1
-
Valve
-
Alarm
-
Normal operation
The condensate drain is operating normally.
L1
On
L2
-
P1
-
Valve
-
Alarm
-
Supply voltage missing
The condensate drain is disconnected from the power supply. The operating functions are
deactivated. An alarm signal is remotely transmitted.
L1
-
L2
-
P1
-
Valve
-
Alarm
On
Standby
There is no condensate. The supply voltage is applied and the condensate drain is ready to
operate. If no condensate is discharged for 3 hours, the software performs a brief forced discharge.
The green LED is continuously on and the condensate drain activates the same routine until there
is a normal discharge that brings the sensor back to the minimum level.
L1
On
L2
-
P1
-
Valve
1.
Off for 3 hours.
2.
On for 2 seconds.
Alarm
-
Automatic condensate discharge
The maximum level is reached. The valve opens (with a delay of 10 seconds) and the condensate
is discharged. The valve closes as soon as the minimum level is reached.